Horner APG XLe OCS HEXE220C014 User Manual

Page 3

background image

MAN0809-09-EN

Specifications / Installation

__________________________________________________________________________________________________________________________________________________________________
12/18/2008

Page 3 of 4 ECN # 947

5

Filter


Filter Constant sets the level of digital filtering according to
the following chart.














60

20

100

40

80

20

0

10

100

90
80
70
60
50
40
30

Scans

0

1

2

3

4

5

6

0

7

%

C

o

m

p

let

e

[

]

Filter
Constant













Digital Filtering. The illustration above demonstrates the

effect of digital filtering (set with Filter
Constant) on module response to a
temperature change.




7

MJ2 Pinouts in Full and Half Duplex Modes

6

I/O Register Map

Registers

Description

%I1 to %I24

Digital Inputs

%I32 Output

Fault

%I25 to %I31

Reserved

%Q1 to %Q16

Digital outputs

%Q17

Clear HSC1 accumulator to 0

%Q18

Totalizer: Clear HSC2

Quadrature 1-2: Accumulator 1

Reset to max – 1

%Q19

Clear HSC3 Accumulator to 0

%Q20

Totalizer: Clear HSC4

Quadrature 3-4: Accumulator 3

Reset to max – 1

%Q21 to %Q32

Reserved

%AI1 to %AI4

Analog inputs

%AI5, %AI6

HSC1 Accumulator

%AI7, %AI8

HSC2 Accumulator

%AI9, %AI10

HSC3 Accumulator

%AI11, %AI12

HSC4 Accumulator

Full Duplex Mode

Half Duplex Mode

Pin

MJ2 Pins

Signal

Direction

8

TXD OUT

7

RXD IN

6

0 V

Ground

5*

+5 60mA

OUT

4

TX- OUT

3

TX+ OUT

2

RX- IN

1

RX+ IN

1

8

* +5 on XLe Rev E and later

Pin

MJ2 Pins

Signal

Direction

8

TXD OUT

7

RXD IN

6

0 V

Ground

5*

+5 60mA

OUT

4

TX- OUT

3

TX+ OUT

2

TX-/RX- IN/OUT

1

TX+/RX+ IN/OUT

1

8

* +5 on XLe Rev E and later

%AQ1, %AQ2

PWM1 Duty Cycle

%AQ3, %AQ4

PWM2 Duty Cycle

%AQ5, %AQ6

PWM Prescale

%AQ7, %AQ8

PWM Period

%AQ9 to %AQ14

Analog outputs

Note: Not all XLe units contain the I/O listed in this table.


Registers

PWM

HSC

Stepper

%AQ1

Start

Frequency

%AQ2

PWM1 Duty

Cycle

(32 bit)

HSC1

Preset

Value

Run

Frequency

%AQ3

%AQ4

PWM2 Duty

Cycle

(32 bit)

HSC2

Preset

Value

Accel Count

(32 bit)

%AQ5
%AQ6

PWM Prescale

(32 bit)

Run Count

(32 bit)

%AQ7
%AQ8

PWM Period

(32 bit)

Decel Count

(32 bit)

%Q1

Run

%I30 Ready/Done
%I31

Error