Horner APG XLe OCS HEXE220C014 User Manual
Page 2
MAN0809-09-EN
Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
12/18/2008
Page 2 of 4 ECN # 947
Section 3 continued
4
Wiring and Jumpers
• Wire according to the type of inputs / outputs used and select
the appropriate jumper option. Use Copper Conductors
in Field Wiring Only, 60/75° C
4.1
I/O Jumpers Settings (JP1 – JP3)
4.2
External DIP Switch Settings (or Jumpers Settings)
4.3
Wiring Examples
J1
Orange
XE103 / XE104
Name
I1 IN1
I2 IN2
I3 IN3
I4 IN4
I5 IN5
I6 IN6
I7 IN7
I8 IN8
H1
HSC1 / IN9
H2
HSC2 / IN10
H3
HSC3 / IN11
H4
HSC4 / IN12
A1 Analog
IN1
A2 Analog
IN2
0V Ground
J2
Black
XE103
XE104
0V Ground
V+ V+
*
NC
No
Connect
OUT13
Q12 OUT12
Q11 OUT11
Q10 OUT10
Q9 OUT9
Q8 OUT8
Q7 OUT7
Q6 OUT6
Q5 OUT5
Q4 OUT4
Q3 OUT3
Q2
OUT2 / PWM2
Q1
OUT1 / PWM1
V+* Supply for Sourcing Outputs
J3
Orange
XE104
I13 IN13
I14 IN14
I15 IN15
I16 IN16
I17 IN17
I18 IN18
I19 IN19
I20 IN20
I21 IN21
I22 IN22
I23 IN23
I24 IN24
0V Ground
8
1
Pin
MJ1 Pins
MJ2 Pins
8
TXD OUT TXD OUT
7
RXD IN RXD IN
6
0
V Ground 0
V Ground
5*
+5
60mA
OUT
+5
60mA
OUT
4
RTS OUT TX- OUT
3
CTS IN TX+ OUT
2
RX- /
TX-
IN /
OUT
RX- IN
1
RX+ /
TX+
IN /
OUT
RX+ IN
Note: The Cscape Module Setup configuration must match
the selected I/O (JP) jumper settings.
I1
0V
001XLE036
12-24VDC
I1
0V
Positive Logic In Negative Logic In
Positive Logic vs. Negative Logic Wiring
The XLE can be wired for Positive Logic inputs or
Negative Logic inputs.
DIPSW3: FACTORY
USE ONLY (tiny
bootloader firmware
downloading). NOT TO
BE USED FOR
NORMAL OCS
OPERATION.
DIPSW2: MJ2
Termination
(Default – none)
DIPSW1: MJ1
Termination
(Default – none)
As seen when looking at the top of the XLe unit:
Memory Slot:
Uses Removable Memory for data logging, screen
captures, program loading and recipes.
Horner Part No.: HE-MC1
Serial Communications:
MJ1: (RS-232 / RS-485) Use for Cscape programming and
Application-Defined Communications.
MJ2: (RS-232 / RS-485) Use for Application-Defined
Communications.
Location of I/O jumpers (JP)
and wiring connectors
(J1 – J4).
Wiring Specifications
For I/O wiring (discrete), use the
following wire type or equivalent:
Belden 9918, 18 AWG (0.8 mm
2
)
or larger.
For shielded Analog I/O wiring,
use the following wire type or
equivalent: Belden 8441, 18
AWG (0.8 mm
2
) or larger.
For CAN wiring, use the
following wire type or equivalent:
Belden 3084, 24 AWG (0.2 mm
2
)
or larger.
Some XLes have jumpers to set RS-485 port
termination, though most use DIP Switches.
The External Jumpers or DIP Switches are used for
termination of the RS-485 ports. The XLe is shipped
un-terminated.
To terminate, select one of the jumpers shipped with
the product and insert it based upon the option that is
desired or, select the switch (as shown in the
illustration) and configure based upon the option that
is desired.
Negative Logic
Positive Logic
JP1 Digital DC Inputs
Default
I1
I2
I3
I4
0V
I5
I6
I7
I8
H1
001XLE046
12-24VDC
LOOP
PWR
20mA
0-10VDC
A1
A2
H2
H3
H4
J1 Orange
Positive Logic
Digital In
Q1
Q2
Q3
Q4
Q9
Q10
Q11
Q12
Q5
Q6
Q7
Q8
V+
0V
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
10 - 30VDC
Q13
001XLE024
LOAD
J2 Black
Positive Logic
Digital Out
Note: The wiring examples show
Positive Logic input wiring.
I13
I14
I15
I16
I22
I23
I24
0V
I17
I18
I19
I20
I21
001XLE047
12-24VDC
J3 Orange
Positive Logic
Digital In
J4
Orange
XE104
Q16 OUT16
Q15 OUT15
Q14 OUT14
XE104 J4 Orange
Positive Logic
Digital Out
Q14
Q15
V+
0V
LOAD
LOAD
10 - 30VDC
Q16
LOAD
J2
J4
Note:
When using JP3 (A1-A2),
e
ach channel can be
independently configured.
Note:
Loop Power requirements
are determined by the
transmitter specification.
J1
J2
J3
JP3
JP1
001XLE005-R1
J4
20mA
10VDC
JP3
CURRENT OR VOLTAGE INPUTS
001XLE043-R1
A1
A2
A1
A2
1
1
2
2
3
3
4
4
001XLE037-R1
* +5Vdc 60mA Max on XLe Rev E and later