Aalborg TIO Totalizer I/O Flow Monitor/Controller User Manual
Page 94
91
UART ERROR CODES
1
Not Supported Command or Back Door is not enabled.
2
Wrong # of Arguments.
3
Address is Out of Range (MR or MW commands).
4
Wrong # of the characters in the Argument.
5
Attempt to Alter Write Protected Area in the EEPROM.
6
Proper Command or Argument is not found.
7
Wrong value of the Argument.
8
Reserved.
9
Manufacture specific info EE KEY (wrong key or key is disabled).
DIAGNOSTIC AND SYSTEM EVENTS CODES AND BIT POSITION
Code
Event Description
Bit position
0
CPU Temp. High
0x0001
1
High Flow Alarm
0x0002
2
Low Flow Alarm
0x0004
3
Range between H-L
0x0008
4
Tot#1 > Limit
0x0010
5
Tot#2 > Limit
0x0020
6
OptPulse Queue
0x0040
7
Flow OverLimit
0x0080
8
Vcc OutOfRange
0x0100
9
SerComm. ERROR
0x0200
A
EEPROM ERROR
0x0400
B
Power on Event
0x0800
C
Password Event
0x1000
D
Fatal Error
0x2000
INTERNAL K-FACTOR TABLE LIST
Index
Gas
K-Factor
1
Ar
1.4573
2
AsH3
0.6735
3
BF3
0.5082
4
Br2
0.8083
5
C2H2
0.5829
6
C2N2
0.6100
7
CH4
0.7175
8
Cl2
0.8600
9
CO2
0.7382
10
COF2
0.5428
11
COS
0.6606
12
CS2
0.6026
13
F2
0.9784
14
H2
1.0106
15
He
1.4540
16
N2O
0.7128
17
NH3
0.7310
18
NE
1.4600
19
NO
0.9900
20
O2
0.9926
21
SO2
0.6900
22
Xe
1.4400