TABLE 6.5 J2 INPUT / OUTPUT JUMPER CONFIGURATION OPTIONS FOR GENERIC
FLOW METERS AND CONTROLLERS
TIO PV TYPE
J2 JUMPER CONFIGURATION
NOTE
Output
Input
J2A
J2B
J2C
J2D
J2E
J2F
0-5Vdc 0-5Vdc
2 - 3
5 - 6
8 - 9
10-11 14-15
17-18
0-5Vdc
4-20
mA
2 - 3
5 - 6
8 - 9
10-11 13-14
16-17
4 – 20
mA
0-5Vdc
1 - 2
4 - 5
7 - 8
10-11 14-15
17-18
4 – 20
mA
4 – 20
mA
1 - 2
4 - 5
7 - 8
10-11 13-14
16-17
N/A
5-10
Vdc
2 - 3
5 - 6
8 - 9
11-12 14-15
17-18
External +5Vdc
reference signal must
be connected to pin 9
0 - 10
Vdc
0 - 10
Vdc
2 - 3
5 - 6
8 - 9
11-12 14-15
17-18
Special Order option!
(PCB hardware must be
changed)
0 - 10
Vdc
4 – 20
mA
2 - 3
5 - 6
8 - 9
10-11 13-14
16-17
Special Order option!
(PCB hardware must be
changed)
4 – 20
mA
0 - 10
Vdc
1 - 2
4 - 5
7 - 8
11-12 14-15
17-18
Special Order option!
(PCB hardware must be
changed)
0-5Vdc
0 - 10
Vdc
2 - 3
5 - 6
8 - 9
11-12 14-15
17-18
Special Order option!
(PCB hardware must be
changed)
0 - 10
Vd
0-5Vdc
2 - 3
5 - 6
8 - 9
10-11 14-15
17-18
Special Order option!
(PCB hardware must be
changed)
NOTE: Your TIO device input / output jumpers were configured at the
factory according to your order. There is no need to change input /
output jumper’s configuration unless different input is being used.
Before applying power and process signals, make sure the input /out
put jumpers are installed in the correct position (See Table 6.5).
,
c) Input/Output Jumper Configuration