3. SPECIFICATIONS
ADC/DAC RESOLUTION:
12 bit.
ACCURACY:
±0.1% F.S.
ANALOG INPUTS:
0-5 Vdc, 4-20 mA, 5-10 Vdc (jumper-selectable),
0-10 Vdc (special order).
ANALOG OUTPUTS:
0-5 Vdc, 4-20 mA (jumper-selectable), 0-10Vdc
(special order).
LCD:
128x64 graphic LCD with instantaneous Flow reading
and Total volume indication. Adjustable LCD contrast
and back light. Refresh rate 10 times/sec.
KEY-PAD:
Local 6 tactical push buttons.
DATA PROTECTION:
EEPROM backup of all settings, backup Totalizer #1
every one second. Data retention at least 10 years.
Password protection for configuration data.
PULSE OUTPUT:
User-programmable, optically-isolated, with preset
active low time interval (10 – 6550 ms), UCE ≤
40Vdc, ICE ≤ 150 mA (Voltage Isolation: 250 Vrms).
DIGITAL OUTPUT:
Two programmable, optically-isolated. UCE ≤ 40Vdc,
ICE ≤ 150 mA (Voltage Isolation: 250 Vrms).
DIGITAL INTERFACE:
RS-232 or RS-485 (multidrop capability up to 64
devices).
POWER REQUIREMENTS: 12 – 26 Vdc, 100 mV maximum peak-to-peak output
noise (up to 60 mA maximum load).
Protocol:
Proprietary ASCII software interface command set.
Speed:
1200 - 2400 - 4800 - 9600 -19200 – 38400 – 57600 – 115200
baud (user-selectable). Default 9600 baud.
Configuration: Stop bit:
1
Data bits:
8
Parity: None
Flow Control:
None
Addressing:
Maximum 255 addresses, default
address 11 hex. (for RS-485 option only).
Type:
RS232 or RS485 2-wire.