Aalborg TIO Totalizer I/O Flow Monitor/Controller User Manual
Page 89
86
COMMAND
NAME
DESCRIPTION
NO.
COMMAND SYNT
A
X
COMMAND
ARGUMENT 1
ARGUMENT 2
ARGUMENT 3
ARGUMENT 4
RESPONSE
K-Factor
Read and set K-Factor relative to
N2
Mode:
D
–
Disabled (K-Factor = 1.0)
I
–
Internal
U –
User
-Defined
14
K
S
(read current settings)
Returns current mode,
index and UD value
KS:Mode,Index,
UDvalue
Example:
KS:U,1,0.91200
D
(Set Mode: Disabled)
KD
I
(Set Mode: Internal Index)
[1-22]
KI:Index,GasName
Example: KI:1,Ar
U
(Set Mode: User
-Defined V
alue)
alue> [0.00001-999.9] KU:V alue Example: KU:0.91200 Calibration Settings Sets/Reads Calibration related variables. Argument 1 = T Hours since last time unit was calibrated. NOTE: must be reset to zero after calibration. 15 C P Flow Power Up Delay [seconds] alue> [seconds] CP: Example: CP:3 No Argument (Returns Current Power Up Delay) CP: Example: CP:3 F Device Full Scale Range in liter/min alue> [liter/min] CF: Example CF:1000.0 No Argument (Returns Current Meter FS Range) CF: Example: CF:1000.0 L Device Low Flow Cut Off in % of full scale alue> (%FS) CL: Example: CL:5.0 No Argument (Returns Current value) CL: Example: CL:5.0 T Read/Reset Calibration/ Maintenance T imer No Argument (read timer) CT : Example: CT :1024.2 Z Set Cal. T imer to Zero CT :Z