Aalborg TIO Totalizer I/O Flow Monitor/Controller User Manual
Page 75
![background image](/manuals/414126/75/background.png)
72
INDEX
NAME
DATA TYPE
NOTES
34
SetPointPFS
float
Set Point value in %FS fraction notation [0.0 - 1.1]
35
DiagEventLatchMask
uint
Diagnostic Events Latch Mask register: Clear bit-> mask
36
Reserved3
float
Device General Reserved Settings
37
Reserved4
float
Device General Reserved Settings
38
OptOut1_Config
uint
Optical Output #1 Configuration (function)
39
OptOut2_Config
uint
Optical Output #2 Configuration (function)
40
GLCD_Mode
uint
Main Process screen mode: 0-Static,1-Dynamic
41
GLCD_Static_Mode
uint
Type of the static LCD screen: [0-3]
42
GLCD_AUTO_Mode_Mask
uint
Type of the AUTO LCD screen: keeps mask for each variable
43
Cycle_Time
uint
Time in seconds for each screen to be displayed in
Dynamic mode
44
GLCD_Contrast
uint
GLCD Contrast settings [1 - 16]
45
GLCD_Reserved
uint
GLCD reserved settings
46
GLCD_LED_PWM
uint
GLCD LED backlight PWM Duty cycle [1-19]
47
PSP_StepMasc
uint
Mask Register for Program SP steps [0x0000 - 0xFFFF]
48
PSP_LoopMode
uint
Program SP Loop mode: 0-disabled, 1-enabled
49
Out_Scale_mA
float
Analog 4-20 mA Out Scale
50
Out_Offset_mA
float
Analog 4-20 mA Out Offset
51
In_mA_Mode
uint
Reserved input parameter
52
In_mA_Reserved
uint
Reserved input parameter
53
In_Scale_mA
float
Analog 4-20 mA Input Scale
54
In_ Offset _mA
float
Analog 4-20 mA Input Offset
55
OutScaleV
float
Flow Analog 0-5/0-10 Vdc Out Scale
56
OutOffsetV
float
Flow Analog 0-5/0-10 Vdc Out Offset
57
InScaleV
float
Flow Analog 0-5/0-10 Vdc Input Scale
58
InOffsetV
float
Flow Analog 0-5/0-10 Vdc Input Offset
59
F_AlarmMode
uint
Flow Alarm Mode (0=Disabled, 1=Enabled)
60
F_LowAlarmPFS
float
Low Flow Alarm in PFS [0-1.0 fraction notation %F.S.]
61
F_HiAlarmPFS
float
High Flow Alarm in PFS [0-1.0 fraction notation %F.S.]
62
F_AlmDelay
uint
Delay in seconds 0-3600 for Flow Alarm action
63
F_AlarmLatch
uint
Flow Alarm Latch
64
F_AlarmSpare
uint
Flow Alarm Spare settings
65
Total1_Mode
uint
Totalizer#1 mode (0-Disabled, 1-Enabled)
66
Total1_Config
uint
Totalizer#1 configuration (0-Count Up)
67
Total1_FlowStart
float
Start tot. at flow [0-1.0 fraction notation %F.S.]
68
Total1_VolStop
float
Limit volume in %s, 0 = disable
69
Total1_PowOnDelay
uint
Totalizer#1 power on delay in second [0-3600]
70
Total1_ValueLock
uint
Lock Totalizer#1 value (0-can be reset, 1-can not be reset)