Aalborg TIO Totalizer I/O Flow Monitor/Controller User Manual
Page 84
81
COMMAND
NAME
DESCRIPTION
NO.
COMMAND SYNT
A
X
COMMAND
ARGUMENT 1
ARGUMENT 2
ARGUMENT 3
ARGUMENT 4
RESPONSE
Optical
Outputs
Assigns action of the two
optical outputs. The optical
outputs can be assigned to:
D
–
No Action (disabled*)
AL
–
Low Flow Alarm
AH –
High Flow Alarm
AR
–
Range between High &
Low Alarms
T1
–
To
t#1 Reading > limit
T2
–
To
t#2 Reading > limit
PO –
Pulse
Output
DE –
Diagnostic
Events
M
–
Manual On (enabled)
9
O
1 (Output #1)
2 (Output #2)
D*
O1:D or O2:D
AL
O1:AL or O2:AL
AH
O1:AH or O2:AH
AR
O1:AR or O2:AR
T1
O1:T1 or O2:T1
T2
O1:T2 or O2:T2
PO
O1:PO or O2:PO
DE
O1:DE or O2:DE
M
O1:M or O2:M
S (read current
settings)
O1:D or O2:PO
Device
Function
Sets / Reads Device Function
Device Function:
M –
Flow
Meter
C –
F
low
Controller
10
DF
alue> M – Flow Meter C – Flow Controller DF: alue> Example: DF:M DF: alue> Example: DF:M No Argument (Returns Current Device Function)