Aalborg TIO Totalizer I/O Flow Monitor/Controller User Manual
Page 82

79
COMMAND
NAME
DESCRIPTION
NO.
COMMAND SYNT
A
X
COMMAND
ARGUMENT 1
ARGUMENT 2
ARGUMENT 3
ARGUMENT 4
RESPONSE
Diagnostic
Events
Mask
Display/Set Diagnostic Events
Mask Register
See list of the Diagnostic
Events below
.
5
DM
NO ARGUMENT
(read current
Diagnostic Events
Mask Register)
DM:0x9FFF
0x9FFF – diagnostic mask
(16 bits wide).
Set bit - Enable
Clear bit - Disable
alue> 0x0000 - 0xFFFF Set new value NOTE: all 6 characters are required DM:0x9FFF Diagnostic Events Latch Mask Display/Set Diagnostic Events Latch Mask register See list of the Diagnostic Events below . 6 DL NO ARGUMENT (read current Diagnostic Events Latch Mask register) DL:0x100F 0x100F – diagnostic latch mask (16 bits wide). Set bit - Enable Clear bit - Disable alue> 0x0000 - 0xFFFF Set new value to Diagnostic Events Latch Mask register . NOTE: all 6 characters are required DL:0x100F 0x100F – diagnostic latch mask (16 bits wide). Set bit - Enable Clear bit - Disable Device Info Read device configuration info: - full scale range (L/min) - device function (M/C) - input settings (V ,C) - output settings (V ,C) - low flow cut off (%F .S.) - power up delay (sec.) 7 DI DI: 100.0,M,V ,V ,2.0,2 100.0 – full scale L/min M – device function (meter) V – input (0-5 Vdc) V – output (0-5 Vdc) 2.0 – Low flow cut off (%F .S.) 2 – flow power on delay (sec.)