Process setup, Coil setup – High Country Tek PLD, Powerline / universal single / dual coil PWM Valve Driver User Manual
Page 41
Part No:-
021-00155 RevD7
PowerLine System Controller User Guide
Page | 41
PowerLine User Guide
Process Setup:
Sets the Ramp Rate for both coil A and B to 3 seconds
Up or Down.
Sets the following options to True:
• Enable “Enable:” Enable input pin is active
• Enable Active High: +12v at the enable input will
enable unit
• Ramp to 0 if Disabled: Ramps if disabled
• More Current = More speed (This option should be
set True whenever in Dual Coil Valve Driver Mode).
This is forced on in the Dual Coil Valve Driver
mode.
• Enable Direction is set to False. The direction is determined by comparing the Command input voltage to the
Center Volts Setting in the Command Range.
• All other process options are grayed out and disabled while in Valve Driver mode.
Coil Setup:
Sets Maximum and Minimum Coil Current to 1200mA and
120mA respectively.
In this instance, the Dither has been disabled with a value of
0%.