beautypg.com

Process setup, Coil setup – High Country Tek PLD, Powerline / universal single / dual coil PWM Valve Driver User Manual

Page 41

background image

Part No:-

021-00155 RevD7

PowerLine System Controller User Guide

Page | 41

PowerLine User Guide






Process Setup:

Sets the Ramp Rate for both coil A and B to 3 seconds
Up or Down.

Sets the following options to True:

• Enable “Enable:” Enable input pin is active
• Enable Active High: +12v at the enable input will

enable unit

• Ramp to 0 if Disabled: Ramps if disabled
• More Current = More speed (This option should be

set True whenever in Dual Coil Valve Driver Mode).
This is forced on in the Dual Coil Valve Driver
mode.

• Enable Direction is set to False. The direction is determined by comparing the Command input voltage to the

Center Volts Setting in the Command Range.

• All other process options are grayed out and disabled while in Valve Driver mode.

Coil Setup:

Sets Maximum and Minimum Coil Current to 1200mA and
120mA respectively.

In this instance, the Dither has been disabled with a value of
0%.