1 power wiring, 2 user input wiring, 3 input wiring 3.4 setpoint (output) wiring – Red Lion CUB5TC User Manual

Page 5: 5 serial communication wiring, 6 usb programming, Com n.o. n.c, Com osnk 1(2) (30 v max.)

background image

5

3.1 POWER WIRING

USR COMM

US

R

+9-28 VDC

TC

-

TC

+

PWR COMMON

+

-

DC Power

+9 to +28 VDC: +VDC
Power Common: -VDC

3.2 USER INPUT WIRING

USR COMM

US

R

+9-28 VDC

TC

-

TC

+

PWR COMMON

Sinking Logic

USR COMM
USR
The user input of the meter is

internally pulled up to +9 to +28 V

with 10 K resistance. The input is

active when it is pulled low (<0 .7 V).

Connect external switching device between the

User Input terminal and User Input Common.

}

3.3 INPUT WIRING

3.4 SETPOINT (OUTPUT) WIRING

COM

N.C.

N.O.

SINGLE SETPOINT RELAY PLUG-IN CARD

COM

N.O.

N.C.

ELECTRICAL CONNECTIONS

DUAL SETPOINT N-FET OPEN DRAIN PLUG-IN CARD

OSNK1

OSNK2

COM

Thermocouple

-

+

TC

-

TC

+

CAUTION: Power input common and sensor input common are NOT isolated

from user input common. In order to preserve the safety of the meter

application, the power input common and the sensor input common must

be suitably isolated from hazardous live earth referenced voltages; or input

common must be at protective earth ground potential. If not, hazardous live

voltage may be present at the User Inputs and User Input Common

terminals. Appropriate considerations must then be given to the potential

of the user input common with respect to earth common; and the common

of the isolated plug-in cards with respect to input common.

COM

OSNK 1(2)

(30 V MAX.)

ELECTRICAL CONNECTIONS

Output Common is not isolated from DC Power Common. Load must

be wired between OSNK terminal and V+ of the load supply.

3.5 SERIAL COMMUNICATION WIRING

N/

C

RS485

2

COMM

A+

B-

N/

C

5

3

4

N/

C

RS232

5

N/

C

TX

N/

C

4 3

COMM

COMM

2

RX

6

1

6

1

3.6 USB PROGRAMMING

USB PROGRAMING PLUG-IN CARD

SERIAL COMMUNICATIONS PLUG-IN CARD

RJ11 CONNECTOR PIN OUTS