6 module 6 - s, Etpoint, Larm – Red Lion PAXDP User Manual
Page 18: Arameters, Parameter menu

18
6-SPt
ACt-n
Setpoint
Select
SPSEL
Setpoint
Value
SP-n
Output
Logic
out-n
HYS-n
Setpoint
Hysteresis
tON-n
On Time
Delay
Off Time
Delay
tOF-n
Standby
Operation
Stb-n
Reset
Action
rSt-n
PAR
Pro
Setpoint
Action
Lit-n
Setpoint
Annunciators
ASn-n
Setpoint
Action
Setpoint
Assignment
6.6 mOdule 6 - s
eTpOinT
(a
larm
) p
arameTers
(
) Ñ
PARAMETER MENU
Repeat programming for each setpoint.
Enter the action for the selected setpoint (alarm output).
See the Setpoint Alarm Figures in the Setpoint Card Bulletin for a visual
detail of each action. The Inside Band action is shown here as it only applies to
the PAXDP.
SETPOINT ASSIGNMENT
Selects the meter value that is used to trigger the Setpoint Alarm. The
settings cause the setpoint to trigger off of the relative (net) input value. The
relative input value is the absolute input value that includes the Display Offset
Value. The
settings cause the setpoint to trigger off of the absolute (gross)
input value. The absolute input value is based on Module 1
and
entries.
SETPOINT ACTION
*
*
*
**
**
SELECT SETPOINT
Select a setpoint (alarm output) to open the remaining module menu. (The
“
” in the following parameters will reflect the chosen setpoint number.) After
the chosen setpoint is programmed, the display will default to
. Select
the next setpoint to be programmed and continue the sequence for each setpoint.
Pressing
PAR at
will exit Module 6.
No Setpoint Action
=
Absolute high, with balanced hysteresis
=
Absolute low, with balanced hysteresis
=
Absolute high, with unbalanced hysteresis
=
Absolute low, with unbalanced hysteresis
=
Deviation high, with unbalanced hysteresis *
=
= Deviation low, with unbalanced hysteresis *
Inside band, with unbalanced hysteresis *
Outside band, with unbalanced hysteresis *
=
=
Lower Totalizer absolute high, unbalance hysteresis **
=
Upper Totalizer absolute high, unbalance hysteresis **
=
* Setpoint 2 or Setpoint 4 deviation and band action setpoints are relative to
the value of setpoint 1 or Setpoint 3 respectively. It is not possible to configure
setpoint 1 or 3 as deviation or band actions. It is possible to use setpoint 1 or 3
for an absolute action, while its value is being used for deviation or band.
** These modes only appear, and are the only modes that appear, when the
setpoint assignment
is set to
. The lower Totalizer action,
,
allows setpoints to function off of the lower 5 digits of the Totalizer. The upper
Totalizer action,
, allows setpoints to function off of the upper 4 digits
of the Totalizer. To obtain absolute low alarms for the Totalizer, program the
or
output logic as reverse.
Ñ
- A setpoint card must be installed in order to access this module.
Setpoint Alarm Figures
With reverse output logic
, the below alarm states are opposite.
ALARM
STATE
OFF
ON
Hys
SP + Hys
SP
OFF
TRIGGER POINTS
Absolute Low Acting (Unbalanced Hys) =
ALARM
STATE
OFF
ON
Hys
SP + ½Hys
SP
SP - ½Hys
OFF
TRIGGER POINTS
ALARM
STATE
OFF
ON
Hys
SP1 + SPn
SP1
OFF
TRIGGER POINTS
Absolute Low Acting (Balanced Hys) =
Deviation High Acting (SP
> 0) =
ALARM
STATE
OFF
ON
Hys
SP + ½Hys
SP
SP - ½Hys
OFF
TRIGGER POINTS
Absolute High Acting (Balanced Hys) =
ALARM
STATE
OFF
ON
Hys
SP
SP - Hys
OFF
TRIGGER POINTS
ALARM
STATE
OFF
ON
Hys
SP1 - SPn
SP1
OFF
TRIGGER POINTS
Absolute High Acting (Unbalanced Hys) =
This is also for Totalizer alarms:
,
Deviation Low Acting (SP > 0) =