beautypg.com

Iring, Eter, Nstalling – Red Lion CUB5 User Manual

Page 4: Ards, 1 power wiring, 2 user input wiring, Wiring overview, Emc installation guidelines

background image

WIRING OVERVIEW

Electrical connections are made via screw-clamp terminals located on the

back of the meter. All conductors should conform to the meter’s voltage and

current ratings. All cabling should conform to appropriate standards of good

installation, local codes and regulations. It is recommended that the power

supplied to the meter (DC or AC) be protected by a fuse or circuit breaker.

Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed

(stranded wires should be tinned with solder.) Insert the lead under the correct

screw-clamp terminal and tighten until the wire is secure. (Pull wire to verify

tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two

#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).

EMC INSTALLATION GUIDELINES

Although this meter is designed with a high degree of immunity to Electro-

Magnetic Interference (EMI), proper installation and wiring methods must be

followed to ensure compatibility in each application. The type of the electrical

noise, source or coupling method into the meter may be different for various

installations. The meter becomes more immune to EMI with fewer I/O

connections. Cable length, routing, and shield termination are very important

and can mean the difference between a successful or troublesome installation.

Listed below are some EMC guidelines for successful installation in an

industrial environment.

1. The meter should be mounted in a metal enclosure, which is properly

connected to protective earth.

2. Use shielded (screened) cables for all Signal and Control inputs. The shield

(screen) pigtail connection should be made as short as possible. The

connection point for the shield depends somewhat upon the application.

Listed below are the recommended methods of connecting the shield, in order

of their effectiveness.

a. Connect the shield only at the panel where the unit is mounted to earth

ground (protective earth).

b. Connect the shield to earth ground at both ends of the cable, usually when

the noise source frequency is above 1 MHz.

c. Connect the shield to common of the meter and leave the other end of the

shield unconnected and insulated from earth ground.

3. Never run Signal or Control cables in the same conduit or raceway with AC

power lines, conductors feeding motors, solenoids, SCR controls, and

heaters, etc. The cables should be ran in metal conduit that is properly

grounded. This is especially useful in applications where cable runs are long

and portable two-way radios are used in close proximity or if the installation

is near a commercial radio transmitter.

4. Signal or Control cables within an enclosure should be routed as far as possible

from contactors, control relays, transformers, and other noisy components.

5. In extremely high EMI environments, the use of external EMI suppression

devices, such as ferrite suppression cores, is effective. Install them on Signal

and Control cables as close to the unit as possible. Loop the cable through the

core several times or use multiple cores on each cable for additional protection.

Install line filters on the power input cable to the unit to suppress power line

interference. Install them near the power entry point of the enclosure. The

following EMI suppression devices (or equivalent) are recommended:

Ferrite Suppression Cores for signal and control cables:

Fair-Rite # 0443167251 (RLC# FCOR0000)

TDK # ZCAT3035-1330A

Steward # 28B2029-0A0

Line Filters for input power cables:

Schaffner # FN610-1/07 (RLC# LFIL0000)

Schaffner # FN670-1.8/07

Corcom # 1 VR3

Note: Reference manufacturer’s instructions when installing a line filter.

6. Long cable runs are more susceptible to EMI pickup than short cable runs.

Therefore, keep cable runs as short as possible.

7. Switching of inductive loads produces high EMI. Use of snubbers across

inductive loads suppresses EMI.

Snubber: RLC# SNUB0000.

4.0 w

irinG

the

M

eter

4.1 POWER WIRING

INP COMM

US

R

+9-28 VDC

INP

B

INP

A

PWR COMMON

+

-

DC Power

+9 to +28 VDC: +VDC
Power Common: -VDC

4.2 USER INPUT WIRING

INP COMM

US

R

+9-28 VDC

INP

B

INP

A

PWR COMMON

Sinking Logic

INP COMM
USR
The user input of the meter is

internally pulled up to +9 to +28 V

with 10 K resistance. The input is

active when it is pulled low (<1 .0 V).

Connect external switching device between the

User Input terminal and Input Common.

}

4

The Plug-in cards are separately purchased option cards that perform specific

functions. The cards plug into the main circuit board of the meter. After

installing the cards, replace the rear cover before wiring the meter.

CAUTION: The Plug-in cards and main circuit board contain static

sensitive components. Before handling the cards, discharge

static charges from your body by touching a grounded bare

metal object. Ideally, handle the cards at a static controlled

clean workstation. Also, only handle the cards by the edges.

Dirt, oil or other contaminants that may contact the cards can

adversely affect circuit operation.

REPLACING THE REAR COVER

To replace the rear cover, align the cover with the input terminals and press

down until the cover snaps into place.

3.0 i

nStallinG

p

luG

-i

n

c

ardS

ECE

ON

4

1

3

2

Setpoint Card

Locking Tab

Comms or

Programming

Card