67 f, D 67, Specifications – Outback Power Systems GS4048A Operators Manual User Manual
Page 69: Table 16 radian inverter settings
Specifications
67
Table 16
Radian Inverter Settings
Field
Item
Default
Minimum
Maximum
(Gen Alert) OFF: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(Gen Alert OFF) Delay
0.5 minutes
0.1 minutes
25.0 minutes
(Vent Fan) ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(Vent Fan) Off Delay
0.5 minutes
0.1 minutes
25.0 minutes
(DC Divert) ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(DC Divert ON) Delay
0.5 minutes
0.1 minutes
25.0 minutes
(DC Divert) OFF: Batt <
44.0 Vdc
40.0 Vdc
56.0 Vdc
(DC Divert OFF) Delay
0.5 minutes
0.1 minutes
25.0 minutes
(AC Divert) ON: Batt >
56.0 Vdc
40.0 Vdc
72.0 Vdc
(AC Divert ON) Delay
0.5 minutes
0.1 minutes
25.0 minutes
(AC Divert) OFF: Batt <
44.0 Vdc
40.0 Vdc
56.0 Vdc
(AC Divert OFF) Delay
0.5 minutes
0.1 minutes
25.0 minutes
Inverter Stacking
Stack Mode
Master
Master, Slave
Power Save
Ranking
Mode = Master:
Master Power Save Level
0
0
31
Mode = Slave:
Slave Power Save Level
1
1
31
Grid-Tie Sell
Grid-Tie Enable
Y
Y or N
Sell Voltage
52.0 Vdc
44.0 Vdc
64.0 Vdc
Module Control
Module Control
GS8048A
Auto
Auto, Left, Right, Both
GS4048A
Left
Auto, Left, Right, Both
Calibrate
Grid AC Input Voltage
X
0 Vac
–7 Vac
7 Vac
Gen AC Input Voltage
X
0 Vac
–7 Vac
7 Vac
Output Voltage
X
0 Vac
–7 Vac
7 Vac
Battery Voltage
X
0.0 Vdc
–0.8 Vdc
0.8 Vdc
Grid Interface Protection Menu
Operating Frequency
Operating Frequency
X
60 Hz
50 Hz, 60 Hz
Stage 1 Voltage Trip
Over Voltage Clearance Time
X
1.0 seconds
0.12 seconds
5.0 seconds
Over Voltage Trip
X
132 Vac
120 Vac
150 Vac
Under Voltage Clearance Time
X
2.0 seconds
0.12 seconds
5.0 seconds
Under Voltage Trip
X
106 Vac
80 Vac
120 Vac
Stage 2 Voltage Trip
Over Voltage Clearance Time
X
0.16 seconds
0.12 seconds
5.0 seconds
Over Voltage Trip
X
144 vac
120 Vac
150 Vac
Under Voltage Clearance Time
X
0.16 seconds
0.12 seconds
5.0 seconds
Under Voltage Trip
X
60 Vac
60 Vac
120 vac
Frequency Trip
Over Frequency
Clearance Time
X
0.16 seconds
0.12 seconds
5.0 seconds
Over
Frequency
Trip
60-Hz system
X
60.5 Hz
60.1 Hz
65.0 Hz
50-Hz system
50.5 Hz
50.1 Hz
55.0 Hz
Under Frequency
Clearance Time
X
0.16 seconds
0.12 seconds
5.0 seconds
Under
Frequency
Trip
60-Hz system
X
59.3 Hz
55.0 Hz
59.9 Hz
50-Hz system
49.3 Hz
45.0 Hz
49.9 Hz
Mains Loss
Clearance Time
X
2.0 seconds
1.0 seconds
5.0 seconds
Reconnect Delay
X
300 seconds
2 seconds
302 seconds
Sell Current Limit
Maximum
Sell Current
GS8048A
X
30 Aac
5 Aac
30 Aac
GS4048A
15 Aac
5 Aac
15 Aac