Specifications

900-0161-01-00 Rev A

65

The

Grid Interface Protection settings are adjustable. However, this is only available to operators with

installer-level access. The reason for this limitation is that there are firm rules concerning the

acceptable voltage range, frequency range, clearance time during power loss, and reconnect delay

when exporting power back to the utility. The rules differ in different locations around the world,

although generally it is expected that the settings cannot be altered by the end user. For this reason,
the installer password must be changed from the default to get access to these settings.

Once this password has been changed, the

Grid Interface Protection settings can be accessed by

using the installer password.
See the

Grid Tied mode on page 15 for more information. Also see

Default Settings and Ranges.

Firmware Revision

This manual applies to inverter models GS8048A and GS4048A with Revision 001.005.xxx or higher.
Updates to the Radian’s firmware are periodically available. These can be downloaded from the

OutBack website www.outbackpower.com. See page 12.

Default Settings and Ranges

NOTES: Certain items are retained at the present setting even when the inverter is reset to factory

defaults. These items are noted with the letter “X” in the Item column.
Certain items, particularly those in the Auxiliary menus, share common set points. If one of these

items is changed in a mode menu, the change will appear in other menus that use the same set point
Certain menus are only visible when the installer password is used, particularly the Grid Interface
Protection menu. These menus are bordered in the table with a double line of this style:

Table 16

Radian Inverter Settings

Field

Item

Default

Minimum

Maximum

INVERTER

Hot Key

Inverter Mode

Off

On, Off, or Search

CHARGER

Hot Key

Charger Control

On

On or Off

AC Input

Hot Key

AC Input Mode

Use

Drop or Use

Search

Sensitivity (see page 23 for increments)

10

0

250

Pulse Length

8 AC Cycles

4 AC Cycles

20 AC Cycles

Pulse Spacing

60 AC Cycles

4 AC Cycles

120 AC Cycles

AC Input and
Current Limit

Input Priority

Grid

Grid or Gen

Grid Input AC Limit

50 Aac

5 Aac

55 Aac

Gen Input AC Limit

50 Aac

5 Aac

55 Aac

Charger AC Limit

GS8048A

30 Aac

0 Aac

30 Aac

GS4048A

15 Aac

0 Aac

15 Aac

Grid AC Input
Mode and Limits

Input Mode

Grid Tied

Generator, Support, Grid Tied, UPS, Backup,

Mini Grid, Grid Zero

Voltage Limit Lower

108 Vac

85 Vac

110 Vac

(Voltage Limit) Upper

132 Vac

125 Vac

140 Vac

Transfer Delay

1.0 second

0.12 seconds

4.0 seconds

Connect Delay

0.2 minutes

0.2 minutes

25.0 minutes

If Mini Grid mode
is selected:

Connect to Grid

48.0 Vdc

44.0 Vdc

64.0 Vdc

(Connect) Delay

10 minutes

2 minutes

200 minutes

If Grid Zero mode
is selected:

DoD Volts

48.0 Vdc

44.0 Vdc

64.0 Vdc

DoD
Amps

GS8048A

5 Aac

1 Aac

30 Aac

GS4048A

5 Aac

1 Aac

15 Aac