65
The
Grid Interface Protection settings are adjustable. However, this is only available to operators with
installer-level access. The reason for this limitation is that there are firm rules concerning the
acceptable voltage range, frequency range, clearance time during power loss, and reconnect delay
when exporting power back to the utility. The rules differ in different locations around the world,
although generally it is expected that the settings cannot be altered by the end user. For this reason,
the installer password must be changed from the default to get access to these settings.
Once this password has been changed, the
Grid Interface Protection settings can be accessed by
using the installer password.
See the
Grid Tied mode on page 15 for more information. Also see
Default Settings and Ranges.
Firmware Revision
This manual applies to inverter models GS8048A and GS4048A with Revision 001.005.xxx or higher.
Updates to the Radian’s firmware are periodically available. These can be downloaded from the
OutBack websi
Default Settings and Ranges
NOTES: Certain items are retained at the present setting even when the inverter is reset to factory
defaults. These items are noted with the letter “X” in the Item column.
Certain items, particularly those in the Auxiliary menus, share common set points. If one of these
items is changed in a mode menu, the change will appear in other menus that use the same set point
Certain menus are only visible when the installer password is used, particularly the Grid Interface
Protection menu. These menus are bordered in the table with a double line of this style:
Table 16
Radian Inverter Settings
Field
Item
Default
Minimum
Maximum
INVERTER
Hot Key
Inverter Mode
Off
On, Off, or Search
CHARGER
Hot Key
Charger Control
On
On or Off
AC Input
Hot Key
AC Input Mode
Use
Drop or Use
Search
Sensitivity (see page 23 for increments)
10
0
250
Pulse Length
8 AC Cycles
4 AC Cycles
20 AC Cycles
Pulse Spacing
60 AC Cycles
4 AC Cycles
120 AC Cycles
AC Input and
Current Limit
Input Priority
Grid
Grid or Gen
Grid Input AC Limit
50 Aac
5 Aac
55 Aac
Gen Input AC Limit
50 Aac
5 Aac
55 Aac
Charger AC Limit
GS8048A
30 Aac
0 Aac
30 Aac
GS4048A
15 Aac
0 Aac
15 Aac
Grid AC Input
Mode and Limits
Input Mode
Grid Tied
Generator, Support, Grid Tied, UPS, Backup,
Mini Grid, Grid Zero
Voltage Limit Lower
108 Vac
85 Vac
110 Vac
(Voltage Limit) Upper
132 Vac
125 Vac
140 Vac
Transfer Delay
1.0 second
0.12 seconds
4.0 seconds
Connect Delay
0.2 minutes
0.2 minutes
25.0 minutes
If Mini Grid mode
is selected:
Connect to Grid
48.0 Vdc
44.0 Vdc
64.0 Vdc
(Connect) Delay
10 minutes
2 minutes
200 minutes
If Grid Zero mode
is selected:
DoD Volts
48.0 Vdc
44.0 Vdc
64.0 Vdc
DoD
Amps
GS8048A
5 Aac
1 Aac
30 Aac
GS4048A
5 Aac
1 Aac
15 Aac