beautypg.com

Module select, Troubleshooting, Table 6 troubleshooting – Outback Power Systems GS4048A Operators Manual User Manual

Page 56

background image

Troubleshooting

54

900-0161-01-00 Rev A

Table 6

Troubleshooting

Symptom

Possible Cause

Possible Remedy

Generator, external

fan, etc. fails to start

when signal is

provided by AUX

output.

AUX output is not connected.

Test the generator or device to confirm functionality. Test the
appropriate AUX terminals with a DVM. (If the RELAY AUX

terminals are in use, test for continuity. If the 12V AUX terminals

are in use, test for 12 Vdc.) If the proper results are present when

the menu indicates the function is

On (and the device still does

not work), then there is an external connection problem. If the

proper results are not present with the function

On, the AUX

circuit may be damaged. Contact OutBack Technical Support.

6

Wrong AUX terminals have

been programmed.

MATE3 system display only: Confirm that the AUX menu that was

programmed matches the terminals that are in use. The

Auxiliary

Output menu programs the 12V AUX terminals. The Auxiliary
Relay
menu programs the RELAY AUX terminals.

Wrong AUX terminals are in use.

If generator or external device requires 12 Vdc, confirm the 12V

AUX terminals have been connected. The RELAY AUX terminals

do not provide voltage.

Advanced

Generator Start

(

AGS) fails to

activate when

conditions are met

(or starts when

conditions are not

met).

MATE3 system display only:

AGS

function does not work if

another valid input is present.

Check both inputs for a second AC source (utility grid). If the

inverter detects an acceptable AC source, it will not allow

AGS.

This is true even if it is internally disconnected from the source
(due to

HBX mode, Mini Grid mode, or similar programming).

MATE3 system display is not
present.

AGS programming is located in the MATE3 and cannot function if
the MATE3 is removed.

Other AUX functions are in

operation.

Gen Alert or another AUX function may try to start or stop the
generator using the wrong criteria. Make sure all other AUX

functions are disabled.

AGS or Gen Alert
functions start the

generator, but the

inverter does not

accept the power

and shuts off the
generator again.

The inverter’s

GRID input is in

use and the input priority is set

to

GRID.

If the input priority is set to

GRID and the

GRID terminals are

energized, an automatically controlled generator will shut down.
This could indicate that the generator has been wired to the

GRID

input, or it could indicate that another AC source is active on
the

GRID input while the generator is using the GEN input.

The

GEN input must be the only terminals in use when

automatically controlling a generator.
Either the

GRID or GEN input can be used when manually

controlling a generator.

Module Select

The GS8048A uses two high-frequency H-Bridge FET modules. The dual design allows half the inverter

to shut down for lower idle consumption. Normally this is automatically selected. If one module fails

or if troubleshooting is otherwise needed, the module selection can be performed manually. The

GS8048A can be directed to use a single, specified module (left or right), or it can be directed to turn

on both modules continuously. This procedure should only be performed if directed by OutBack
Technical Support

6

.

Although the GS4048A has only a single module, this command is still available. The default setting is

Left, which is the location of the module. Do not change this setting in the GS4048A.
The Module Select menu options are displayed as part of Table 16, which begins on page 65.

6

See inside front cover of this manual.

This manual is related to the following products: