beautypg.com

Generator input, Transfer, E 25 fo – Outback Power Systems GS4048A Operators Manual User Manual

Page 27: Operation

background image

Operation

900-0161-01-00 Rev A

25

Gen AC Input Mode and Limits). The settings are titled Voltage Limit Lower and Upper. When adjusted,
they apply equally to L1 and L2. There can be side effects to changing the range of allowed voltages.

Each of the AC inputs has a settable

Connect Delay. This is intended as a warmup period which allows an

input source to stabilize before connection.

∼ The default setting for the

Grid input is 0.2 minutes (12 seconds).

∼ The default setting for the

Gen input is 0.5 minutes (30 seconds).

These items are adjustable in the appropriate menu of the MATE3 (

Grid AC Input Mode and Limits or Gen

AC Input Mode and Limits).

NOTES:

The

Grid Tied input mode does not use these acceptance limits and uses the Grid Interface Protection

settings instead. (See page 17 for more information.) The inverter may not accept AC power if it meets the
settings noted here but does not meet the

Grid Interface Protection settings.

AC acceptance is controlled separately between the Radian inverter’s two inputs. An AC source that is
unacceptable on one input may be acceptable on the other if the input mode or settings are different.

Certain input modes

s

uch as

Mini Grid may prevent the inverter from accepting AC power even if electrical

conditions are met. (See page 18.)

Several items external to the inverter may prevent the inverter from accepting AC power even if electrical
conditions are met. Some examples are the

High Battery Transfer, Grid Usage Time, or Load Grid Transfer

functions, all of which are operated by the MATE3 system display. (See page 45.) Another example is the
MATE3’s

AC INPUT hot key menu, which can order all inverters to disconnect when set to Drop.

Generator Input

A generator should be sized to provide enough power for all inverters, both for loads and for battery

charging. The generator’s voltage and frequency must match the inverter’s acceptance settings.
It is usually recommended that the generator be sized at twice the wattage of the inverter system.
Many generators may not be able to maintain AC voltage or frequency for long periods of time if they

are loaded more than 80% of rated capacity.
The generator is required to have a stable output before its power is accepted by the inverter. Some
generators with less stable or uneven outputs may not be accepted. The use of the

Generator input

mode may assist with this problem.

Transfer

The inverter uses a transfer relay to alternate between the states of inverting and of accepting an AC

source. Until the relay energizes, the output terminals are electrically isolated from the input that is in
use. When it closes, the input and output terminals become electrically common. (The terminals for

the unused input remain isolated during this time.) When the relay changes states, the physical

transfer delay is approximately 25 milliseconds.

CAUTION: Equipment Damage

Current draw in excess of the transfer relay rating can damage the transfer relay. This

damage is not covered by warranty. Use protective devices of appropriate size.

This manual is related to the following products: