Troubleshooting

50

900-0161-01-00 Rev A

Table 6

Troubleshooting

Symptom

Possible Cause

Possible Remedy

Inverter set to

Search (Search

mode).

MATE3 system display only: If constant power is required, set to

On

with the INVERTER

hot key. (If this setting was intentional, then

no action is required.)

One or more units

have no output but

others do (in multi-

inverter system).

Unit is slave and is in Power

Save mode.

MATE3 system display only: Check Power Save levels in
the

Inverter Stacking menu and test with loads. Determine if the

inverter comes on at the appropriate levels. (If this setting was

intentional, then no action is required.)

Will not connect to

the AC source.

No AC input.

Check the AC voltage on the inverter’s input test points. (See

page 49.) If not present, the problem is external. If present, the

inverter could be damaged. Contact OutBack Technical Support.

4

The L1 output is wired to its L2

input, or the other way around.
The problem is accompanied by

shifts in frequency.

Disconnect the wires from the inverter’s AC input terminals or AC

output terminals, or both. If the problem immediately disappears,
it is an external wiring issue. The inverter’s input and output

terminals must remain isolated from each other.

AC source does not meet

requirements.

MATE3 system display only: Check the

Last AC Disconnect screen

(using the AC INPUT

hot key and the Discon selection) for the

reason for disconnection. If the unit never originally connected,
check the

Warning menu (using the Inverter soft key from the

Home screen). Confirm source voltage and frequency.

AC source meets requirements

but is “noisy” or irregular.

MATE3 system display only: The

Generator input mode can accept

irregular AC power. Select that mode for that input.

Inverter was manually set to

disconnect from AC.

MATE3 system display only: Change the AC Input Control setting
from

Drop to Use with the AC INPUT hot key. (If this setting

was intentional, then no action is required.)

Grid use function has

disconnected from AC.

MATE3 system display only: If activated prematurely, check the
MATE3’s

Grid Use Time settings and the MATE3 clock settings. (If

this setting was intentional, then no action is required.)

High Battery Transfer
(

HBX) mode has disconnected

from AC.

MATE3 system display only: Check the AC INPUT hot key screen
to see if

HBX mode is in use. If activated prematurely, check the

settings of

HBX mode. (If this setting was intentional, then no

action is required.)

Mini Grid input mode has

disconnected from AC.

MATE3 system display only: Check the

Inverter part of the Settings

menu to see if

Mini Grid mode is in use. If activated prematurely,

check the settings of

Mini Grid mode. (If this setting was

intentional, then no action is required.)

Conflicting programming.

MATE3 system display only: Check to see if more than one of these

is enabled:

Mini Grid, HBX, Grid Use Time, Load Grid Transfer.

These have conflicting priorities. Only one can be used at a time.

Grid Tied mode has

disconnected from AC.

AC source does not meet requirements; see related entry under

“Will not sell power to the utility grid” (next page).