Specifications

66

900-0161-01-00 Rev A

Table 16

Radian Inverter Settings

Field

Item

Default

Minimum

Maximum

Gen AC Input
Mode and Limits

Input Mode

Generator

Generator, Support, Grid Tied, UPS, Backup,

Mini Grid, Grid Zero

Voltage Limit Lower

108 Vac

85 Vac

110 Vac

(Voltage Limit) Upper

140Vac

125 Vac

140 Vac

Transfer Delay

1.0 second

0.12 seconds

4.0 seconds

Connect Delay

0.5 minutes

0.2 minutes

25.0 minutes

If Mini Grid mode
is selected:

Connect to Grid

48.0 Vdc

44.0 Vdc

64.0 Vdc

(Connect) Delay

10 minutes

2 minutes

200 minutes

If Grid Zero mode
is selected:

DoD Volts

48.0 Vdc

44.0 Vdc

64.0 Vdc

DoD
Amps

GS8048A

5 Aac

1 Aac

30 Aac

GS4048A

5 Aac

1 Aac

15 Aac

AC Output

Output Voltage

X

120 Vac

100 Vac

130 Vac

AC Coupled Mode

This selection is inoperative

Low Battery

Cut-Out Voltage

42.0 Vdc

36.0 Vdc

48.0 Vdc

Cut-In Voltage

50.0 Vdc

40.0 Vdc

56.0 Vdc

Battery Charger

Absorb Voltage

57.6 Vdc

44.0 Vdc

64.0 Vdc

(Absorb) Time

1.0 hours

0.0 hours

24.0 hours

Float Voltage

54.4 Vdc

44.0 Vdc

64.0 Vdc

(Float) Time

1.0 hours

0.0 hours

24/7

Re-Float Voltage

50.0 Vdc

44.0 Vdc

64.0 Vdc

Re-Bulk Voltage

49.6 Vdc

44.0 Vdc

64.0 Vdc

Battery Equalize

Equalize Voltage

58.4 Vdc

44.0 Vdc

68.0 Vdc

(Equalize) Time

1.0 hours

0.0 hours

24.0 hours

Auxiliary Output

Aux Control

Auto

Off, Auto or On

Aux Mode

Vent Fan

Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,

DC Divert, GT Limits, Source Status, AC Divert

(Load Shed) ON: Batt >

56.0 Vdc

40.0 Vdc

72.0 Vdc

(Load Shed ON) Delay

0.5 minutes

0.1 minutes

25.0 minutes

(Load Shed) OFF: Batt <

44.0 Vdc

40.0 Vdc

56.0 Vdc

(Load Shed OFF) Delay

0.5 minutes

0.1 minutes

25.0 minutes

(Gen Alert) ON: Batt <

44.0 Vdc

40.0 Vdc

56.0 Vdc

(Gen Alert ON) Delay

0.5 minutes

0.1 minutes

25.0 minutes

(Gen Alert) OFF: Batt >

56.0 Vdc

40.0 Vdc

72.0 Vdc

(Gen Alert OFF) Delay

0.5 minutes

0.1 minutes

25.0 minutes

(Vent Fan) ON: Batt >

56.0 Vdc

40.0 Vdc

72.0 Vdc

(Vent Fan) Off Delay

0.5 minutes

0.1 minutes

25.0 minutes

(DC Divert) ON: Batt >

56.0 Vdc

40.0 Vdc

72.0 Vdc

(DC Divert ON) Delay

0.5 minutes

0.1 minutes

25.0 minutes

(DC Divert) OFF: Batt <

44.0 Vdc

40.0 Vdc

56.0 Vdc

(DC Divert OFF) Delay

0.5 minutes

0.1 minutes

25.0 minutes

(AC Divert) ON: Batt >

56.0 Vdc

40.0 Vdc

72.0 Vdc

(AC Divert ON) Delay

0.5 minutes

0.1 minutes

25.0 minutes

(AC Divert) OFF: Batt <

44.0 Vdc

40.0 Vdc

56.0 Vdc

(AC Divert OFF) Delay

0.5 minutes

0.1 minutes

25.0 minutes

Auxiliary
Relay

Aux Control

Auto

Off, Auto or On

Aux Mode

Gen Alert

Load Shed, Gen Alert, Fault, Vent Fan, Cool Fan,

DC Divert, GT Limits, Source Status, AC Divert

(Load Shed) ON: Batt >

56.0 Vdc

40.0 Vdc

72.0 Vdc

(Load Shed ON) Delay

0.5 minutes

0.1 minutes

25.0 minutes

(Load Shed) OFF: Batt <

44.0 Vdc

40.0 Vdc

56.0 Vdc

(Load Shed OFF) Delay

0.5 minutes

0.1 minutes

25.0 minutes

(Gen Alert) ON: Batt <

44.0 Vdc

40.0 Vdc

56.0 Vdc

(Gen Alert ON) Delay

0.5 minutes

0.1 minutes

25.0 minutes