N table 5, E 44, Operation – Outback Power Systems GS4048A Operators Manual User Manual

Page 46: Table 5 aux mode functions

background image

Operation

44

900-0161-01-00 Rev A

Note that even if every function in the menu is set to

Off, external programming from other devices

may still activate the AUX output. An example is the system display’s AGS function (see page 45).

The AUX functions are summarized in Table 5.

Table 5

Aux Mode Functions

Name

Purpose

Triggers

Settable

Points

Start

Stop

Load
Shed

Operates designated loads

normally; turns off loads in

severe conditions

High Vdc

Low Vdc

High temp

Low output Vac

High input Aac

Low & high Vdc

On & Off delay

Gen Alert Starts generator to charge

batteries

Low Vdc

High Vdc

Low & high Vdc

On & Off delay

Fault

Signals that the Radian shut

down due to error

Error present

Error cleared

None

Vent Fan Runs fan to vent batteries

while charging

High Vdc

Below high Vdc

High Vdc

Off delay

Cool Fan Runs fan to cool Radian

Internal sensor > 60°C

Internal sensor < 49°C

None

DC Divert Turns on DC dump load to

prevent overcharging

High Vdc

Low Vdc

Low & high Vdc

On & Off delay

GT Limits Signals disconnect of grid-tied

Radian due to AC conditions

GIP parameters

not met

GIP parameters met

None

Source
Status

Signals that the Radian

accepted an AC source

AC source accepted

AC source

disconnected

None

AC Divert Turns on AC dump load to

prevent overcharging

High Vdc

AC source accepted

Low Vdc

High output load

High temperature

Low & high Vdc

On & Off delay