N table 5, E 44, Operation – Outback Power Systems GS4048A Operators Manual User Manual
Page 46: Table 5 aux mode functions
Operation
44
Note that even if every function in the menu is set to
Off, external programming from other devices
may still activate the AUX output. An example is the system display’s AGS function (see page 45).
The AUX functions are summarized in Table 5.
Table 5
Aux Mode Functions
Name
Purpose
Triggers
Settable
Points
Start
Stop
Load
Shed
Operates designated loads
normally; turns off loads in
severe conditions
High Vdc
Low Vdc
High temp
Low output Vac
High input Aac
Low & high Vdc
On & Off delay
Gen Alert Starts generator to charge
batteries
Low Vdc
High Vdc
Low & high Vdc
On & Off delay
Fault
Signals that the Radian shut
down due to error
Error present
Error cleared
None
Vent Fan Runs fan to vent batteries
while charging
High Vdc
Below high Vdc
High Vdc
Off delay
Cool Fan Runs fan to cool Radian
Internal sensor > 60°C
Internal sensor < 49°C
None
DC Divert Turns on DC dump load to
prevent overcharging
High Vdc
Low Vdc
Low & high Vdc
On & Off delay
GT Limits Signals disconnect of grid-tied
Radian due to AC conditions
GIP parameters
not met
GIP parameters met
None
Source
Status
Signals that the Radian
accepted an AC source
AC source accepted
AC source
disconnected
None
AC Divert Turns on AC dump load to
prevent overcharging
High Vdc
AC source accepted
Low Vdc
High output load
High temperature
Low & high Vdc
On & Off delay