beautypg.com

Fcc information to the user, Specification compliance, Specifications – Outback Power Systems GS4048A Operators Manual User Manual

Page 66

background image

Specifications

64

900-0161-01-00 Rev A

FCC Information to the User

This equipment has been tested and found to comply with the limits for a Class B digital device when

powered by a DC source, pursuant to part 15 of the FCC Rules. These limits are designed to provide

reasonable protection against harmful interference in a residential installation. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance

with the instructions, may cause harmful interference to radio communications. However, there is no

guarantee that interference will not occur in a particular installation. If this equipment does cause

harmful interference to radio or television reception, which can be determined by turning the

equipment off and on, the user is encouraged to try to correct the interference by one or more of the

following measures:

Reorient or relocate the receiving antenna.

Increase the separation between the equipment and the receiver.

Connect the equipment to a circuit different from that to which the receiver is connected.

Consult the dealer or an experienced radio/TV technician for help.

Specification Compliance

Inverters intended for grid-interactive use in the United States and Canada must comply with the

established standards of UL 1741 and IEEE 1547 and 1547.1. These standards provide regulation for

acceptable output voltage ranges, acceptable output frequency, total harmonic distortion (THD) and

anti-islanding performance when the inverter is exporting power to a utility source.
The OutBack grid-interactive models are tested using the procedures listed in IEEE 1547.1 to the

standards listed in both UL 1741 and IEEE 1547. The following specifications have been validated

through compliance testing and refer to exporting power to a simulated utility source of less than 1%

voltage total harmonic distortion (THD).

The inverter output exceeds the minimum power factor of 0.85 with a typical power factor of 0.96 or better.

The individual harmonics do not exceed the limits specified in Table 3 of IEEE 1547 Section 4.3.3.

The THD of the root mean square (RMS) current is less than 5%.

The inverter ceases to export power to the simulated utility source under islanding conditions specified in
IEEE 1547 Section 4.4.1.

The inverter also ceases to export power to the simulated utility source after the output voltage or
frequency of the simulated utility source are adjusted to each of the conditions specified in IEEE 1547
Section 4.2.3 Table 1 and Section 4.2.4 Table 2 within the times specified in those tables. All GS8048A and
GS4048A inverters are tested to comply with the table below.

Table 15

Interconnection Response Times to Abnormal Voltages or Frequencies

Voltage Range

(AC Volts)

Frequency

(Hz)

Seconds
Allowed

Cycles

Allowed

V < 60.0

60.0

0.16

9.6

60.0 < V < 105.6

60.0

2.0

120.0

105.6 < V < 132.0

60.0

no cessation

no cessation

132.0 < V < 144.0

60.0

1.0

60.0

V > 144.0

60.0

0.16

9.6

120.0

< 59.3

0.16

9.6

120.0

> 60.5

0.16

9.6

The reconnection delay has a default setting of 5 minutes. The grid-interactive default settings are
shown in the

Grid Interface Protection Menu portion of Table 16.

This manual is related to the following products: