beautypg.com

Troubleshooting, Basic troubleshooting, Ge 49 – Outback Power Systems GS4048A Operators Manual User Manual

Page 51

background image

900-0161-01-00 Rev A

49

Troubleshooting

Basic Troubleshooting

Table 6 is organized in order of common symptoms, with a series of possible causes. Each cause also
shows possible troubleshooting remedies, including system display checks where appropriate.

-

Figure 15

AC Test Points

WARNING: Shock Hazard

During an error shutdown, the inverter’s output terminals are not live. However,

if the inverter recovers from a shutdown, the terminals will become live without
notice. Several error shutdowns can be recovered automatically, including

Low

Battery V, High Battery V, and Over Temperature. See page 55.

Table 6

Troubleshooting

Symptom

Possible Cause

Possible Remedy

No AC output

(will not invert).

No DC voltage.

Use a DC voltmeter to check the voltage directly on the DC
terminals. If not present, the problem is external. If present, the

inverter could be damaged. Contact OutBack Technical Support.

3

Jumper J3 missing.

See the Installation Manual for the location of J3. Confirm the
jumper is present. If missing, replace the jumper. Or follow the

Installation Manual instructions to install an external switch.

Unit defaulted off
(No MATE3 present; initial

install; J3 confirmed present).

The Radian inverter is given an initial Off command in the factory.
With DC present, use narrow pliers to remove jumper J3 from its

pins. Once removed, install it again. This is the equivalent of

“jiggling the switch.”

Inverter set to

Off.

MATE3 system display only: Set to

On with the INVERTER hot key.

3

See inside front cover of this manual.

Metal pads are located at

these locations.

In troubleshooting, AC

voltages can be measured at

this series of test points.

This manual is related to the following products: