Operation

22

900-0161-01-00 Rev A

The following items will affect the inverter’s operation. These are only used when the inverter is

generating AC power on its own.

Low Battery Cut-Out: This function prevents the inverter from draining the batteries completely. When the
DC voltage drops below a specified level for 5 minutes, the inverter will stop functioning. The MATE3 will
give a

Low Battery V error. This is one of the error messages described on page 55. It appears as an event

on the MATE3 system display.

This function is intended to protect both the batteries and the inverter’s output. (Continuing to invert on a
low DC voltage may produce a distorted waveform.) This item is adjustable.

Low Battery Cut-In: The recovery point from Low Battery Cut-Out. When the DC voltage rises above this
point for 10 minutes, the error will clear and the inverter will resume functioning. This item is adjustable.
∼ Connecting an AC source for the Radian to charge the batteries will also clear a low battery error.

Output Voltage: The AC output voltage can be adjusted. Along with small changes, this allows the inverter
to be used for different nominal (split-phase) voltages such as 100/200 Vac and 120/240 Vac.

IMPORTANT:

The output voltage can adjusted to a different nominal value for a particular region.

Making this change will not affect the default input voltage range accepted by the

inverter from an AC source. The input range must be adjusted manually. These

changes should be made at the same time. (See AC Source Acceptance on page 24.)

The inverter is also controlled by a high battery cut-out limit. If the DC voltage rises above this limit, the
inverter will immediately stop functioning and give a

High Battery V error. This is one of the error messages

described on page 55. The shutdown occurs to protect the inverter from damage due excessive DC voltage.
It appears as an event on the MATE3 system display.

∼ For the Radian inverter, the high battery cut-out voltage is 68 volts. It cannot be changed.
∼ If the voltage drops below this point, the inverter automatically recovers.

AC Frequency

CAUTION: Equipment Damage

Setting the inverter’s output frequency to deliver 50 Hz to 60-Hz loads, or setting it to

deliver 60 Hz to 50-Hz loads, could damage sensitive devices. Make certain the

inverter’s output frequency matches the installation.

The inverter’s output can operate at a frequency of either 60 or 50 hertz. This output frequency (and
the AC acceptance frequency) can be changed with the

Operating Frequency menu item. This

requires high-level access. Due to the possibility of damage, access to this setting was restricted by
placing it in the

Grid Interface Protection menu.

The installer password must be changed from the default in order to get access to this menu. Once
this password has been changed, the

Grid Interface Protection menu can only be accessed by using

the installer password. This password can be changed in the system display.

See page 17 for more information on the

Grid Interface Protection menu. See Table 16, which begins

on page 65, for the location of the

Operating Frequency menu item.