beautypg.com

Power save, E 38, Operation – Outback Power Systems GS4048A Operators Manual User Manual

Page 40: Important, Figure 9 power save levels and loads

background image

Operation

38

900-0161-01-00 Rev A

Power Save

Each inverter consumes approximately 30 watts of idle power while it remains on, even if it is not

actively inverting or charging. The Power Save function allows the option to put part of a parallel

system into a quiescent state known as Silent mode. This mode minimizes the idle consumption.
The inverters will come on again when the loads require power. (The term “Silent” is also used in an

unrelated context during battery charging. See page 30.)

When the load increases by approximately 2.5 kW, the master inverter activates one or more additional
modules for assistance. When the load decreases to a lesser wattage (as detected by the master), the
modules deactivate and return to Silent mode. Additional load increments of approximately 2.5 kW will
activate additional modules.

The first module in the master does not enter Silent mode. It remains active unless specifically turned off.

The order in which additional modules activate (or return to Silent mode) is controlled by programming in
the MATE3. The inverters are given a “rank”, or level number. Lower rank numbers activate when lesser
loads are applied. Higher ranks only activate when the load increases to a high level.

IMPORTANT:

Power Save functionality is different between Radian models. The Radian GS4048A
contains only one 4kW module. Activating one module is the same as activating the full
inverter. The GS8048A contains two modules and operates differently. Do not confuse
the behavior of each. See Figure 10 and Figure 11 for differences.

Figure 9

Power Save Levels and Loads

The actual watt and ampere thresholds for activating each model are depicted on the following pages.

IMPORTANT:

It is highly recommended to use the MATE3 Configuration Wizard to set up this function.
It is essential to set the slave Power Save Levels in sequential order. Failure to set them
up correctly will cause erratic system performance. The Configuration Wizard
automatically programs the correct priorities. (See the MATE3 owner’s manual.)

To set these items manually without the Configuration Wizard:
In the MATE3 system display, the

Power Save Ranking screen uses Power Save Level selections to

assign inverter ranks. The screen reads

Master Power Save Level or Slave Power Save Level,

Master

Slave 1

Slave 3

Slave 2

Off

Off

Off

On

Off

Off

On

On

Off

On

On

On

On

On

On

Increasing load

Minimal load

High load

On

Maximum load

This manual is related to the following products: