beautypg.com

Troubleshooting, Table 6 troubleshooting – Outback Power Systems GS4048A Operators Manual User Manual

Page 53

background image

Troubleshooting

900-0161-01-00 Rev A

51

Table 6

Troubleshooting

Symptom

Possible Cause

Possible Remedy

Conflicting AC sources. Priority
input is interfering with

secondary input.

If AC is present on the priority input, the inverter will not connect
to AC on the second input. This is true even if the first input is not

connected for other reasons (programming, low power quality).

Low charge rate.

Charge complete or nearly

complete.

Check the DC voltage and charging stage using the MATE3, if

present. Confirm with DC voltmeter.

MATE3’s DC meter reads
significantly higher than actual

battery voltage.

Check the DC voltage on the inverter’s DC terminals. If different
from the MATE3 reading, the inverter could be damaged.

Otherwise, check the DC voltage on batteries with a voltmeter. If

different from the reading on the inverter, this could be a DC

connection problem.

High output loads.

If total loads and charge exceed the AC input setting, charge rate

decreases to give priority to the loads. Turn off some of the

output loads and test the charge rate again.

High temperature.

The inverter will reduce the current rate for charging and other

activities if the internal temperature exceeds a certain level.

Check temperature readings and allow the inverter to cool if

necessary. (See page 57.) External cooling may also be applied.

Will not charge.

No AC input.

See “Will not connect to AC” category.

Charger set to

Off.

MATE3 system display only: Check the

Charger Mode screen with

the CHARGER

hot key and set to On or Auto. (If this setting was

intentional, then no action is required.)

Grid Zero mode in use.

MATE3 system display only: The charger is inoperative in

Grid Zero

mode. (If this setting was intentional, then no action is required.)

Will not sell power
to the utility grid.

Grid-tied function has been
manually disabled.

MATE3 system display only: Check the

Grid-Tie Enable setting in

the

Grid-Tie Sell menu. Confirm it is set to Y.

Grid Tied mode not in use on

the appropriate input.

MATE3 system display only: Check the

Inverter part of the Settings

menu to see if

Grid Tied mode is in use. Confirm that it has been

selected for the correct Radian input terminals.

AC source does not meet
requirements; this item is

usually accompanied by

disconnecting from the

utility grid when in

Grid Tied

mode.

Verify grid voltage and frequency. Determine if they are within
the inverter’s approved limits. If not, the inverter is operating

correctly. Contact the utility company if necessary.
MATE3 system display only: The program limits are found in the

inverter’s

Grid Interface Protection menu. See the Grid Tied

mode beginning on page 15 for more information on this menu.

The inverter has other criteria

besides the AC source which

must be met, such as the

qualifying time.

MATE3 system display only: Check

Sell Status screen using the

Home screen’s soft keys. The inverter may be operating correctly.

Depending on the conditions which need to be met, the delay

may be temporary,

The inverter will perform the

Offset function before

attempting to sell.

Output loads can consume all excess renewable power if they are

large enough. (The Offset function “sells to the loads.”) Turn off

some output loads and observe the sell operation.



This manual is related to the following products: