beautypg.com

Commissioning, Functional test, Pre-startup procedures – Outback Power Systems GS4048A Operators Manual User Manual

Page 11: Startup

background image

900-0161-01-00 Rev A

9

Commissioning

Functional Test

WARNING: Shock Hazard and Equipment Damage

The inverter cover must be removed to perform these tests. The components are close together and carry

hazardous voltages. Use appropriate care to avoid the risk of electric shock or equipment damage.

Pre-startup Procedures

1. Ensure all DC and AC overcurrent devices are opened, disconnected, or turned off.
2. Double-check all wiring connections.
3. Confirm that the total load does not exceed the inverter’s wattage. (See pages 21 and 55.)
4. Inspect the work area to ensure tools or debris have not been left inside.
5. Using a digital voltmeter (DVM) or standard voltmeter, verify battery voltage. Confirm the

voltage is correct for the inverter model. Confirm the polarity.

6. Connect the MATE3 system display, if present.

Startup

It is highly recommended that all applicable steps be performed in the following order. However, if

steps are inapplicable, they can be omitted.
If the results of any step do not match the description, see the Troubleshooting section on page 49.
To start a single-inverter system:
1. Close the main DC circuit breakers (or connect the fuses) from the battery bank to the inverter.

Confirm that the system display is operational, if present.

CAUTION: Equipment Damage

Incorrect battery polarity will damage the inverter. Excessive battery voltage also may damage the inverter.

This damage is not covered by the warranty.

CAUTION: Equipment Damage

Use of a three-phase AC source may damage the inverter. This damage is not covered by the warranty.

IMPORTANT:

Prior to programming (see Startup), verify the operating frequency of the AC source. This is necessary for

correct AC operation. The default setting is 60 Hz, but this can be changed to 50 Hz.

This manual is related to the following products: