Specifications 114

Switching or disconnecting devices should not be in the earthed circuit conductor between the

DC source and the point of connection of the earthing electrode conductor.

CAUTION:

To reduce the risk of electric shock or energy hazards:

This equipment must be installed by trained service personnel, as defined by the NEC and IEC

60950-1, Second Edition, the standard for Safety of Information Technology Equipment.

Connect the equipment to a reliably grounded safety extra low voltage (SELV) source. An SELV

source is a secondary circuit that is designed so normal and single fault conditions do not
cause the voltages to exceed a safe level (60 V direct current).

The branch circuit overcurrent protection must be rated 20A.

Hot-plug power supply calculations

For hot-plug power supply specifications and calculators to determine electrical and heat loading for the

server, refer to the HP Enterprise Configurator website (

http://h30099.www3.hp.com/configurator/

).