beautypg.com

American Dryer Corp. AD-15 Phase 7 User Manual

Page 9

background image

113243-1

www.amdry.com

7

Illus. C

IMPORTANT:

No more than eight (8) dryers maximum should

be connected to one (1) main common duct

with a vertical run.

VERTICAL VENTING

When vertical single 10-inch (25.4 cm) venting is used (refer

to Illus. B below), the ductwork from the dryer to the outside

outlet cannot exceed 60 feet (18.28 meters), refer to Illus. B

below. This calculation compensates for the use of a

maximum of three (3) elbows including the two (2) elbows

creating the 180° (turned downward) outside outlet.

Illus. B

If the length of the duct run or quantity of elbows used exceeds

the above noted specifications, the cross section area of the

ductwork must be increased in proportion to the number of

elbows or duct run added.

IMPORTANT:

For extended ductwork runs, the cross section

area of the duct can only be increased to an

extent. For extended ductwork runs, a

professional heating, ventilating, and

air-conditioning (HVAC) firm should be

consulted for proper venting information.

MULTIPLE DRYER (COMMON) VENTING

If it is not feasible to provide separate exhaust ducts for each

dryer, ducts for individual dryers may be channeled into a

common main duct. Each dryer is provided with a back draft

damper. The individual ducts should enter the bottom or

side of the main duct at an angle not more than 45° in the

direction of the airflow.

The main common duct may be any shape provided that the

minimum cross-sectional area is maintained. The main duct

should be tapered with the diameter increasing before each

individual 8-inch (20.32 cm) duct is added (refer to Illus. C

below).

NOTE:

Distance between dryer single ducts being

connected to the main common duct must be

a minimum of 31-3/8” (79.69 cm) dryer width.

Ductwork should be laid out in such a manner

where allowances are made at rear area of the

dryer for removal of rear service panels or guards.

!

!

!