MANUAL RESET BURNER

HI-LIMIT INSTRUCTIONS

PHASE 7

This dryer was manufactured with a manual reset burner hi-

limit thermostat, which is monitored by the Phase 7 computer.

If the burner hi-limit is open prior to the start of the drying

cycle, the dryer will start momentarily and then shut down,

the Phase 7 computer will display “BURNER HIGH LIMIT

FAULT” with an audio indication.

If the burner hi-limit opens during a drying cycle, the Phase 7

computer will also display the same error code described

above, along with an audio indication. If the drum temperature

is above 100° F (38° C), the dryer will continue to run with no

heat for 3 minutes or until the drum temperature has dropped

below 100° F (38° C). The clear/stop button on the Phase 7

keyboard (touch pad) must be pressed to clear the error

condition. The open burner hi-limit must be reset “manually”

prior to the start of the next cycle.

Dual Timer

This dryer was manufactured with a manual reset burner hi-

limit thermostat. If the burner hi-limit is open prior to the start

of the drying cycle, or during the cycle, the dryer will not

recognize the open state of the burner hi-limit and will start

or continue through the drying cycle with no heat. Manual

reset hi-limit must be reset manually.

This hi-temperature condition may be caused due to a

restricted exhaust, poor airflow, or improper burner operation.

The location of the burner hi-limit is on the right side of the

burner box, looking at the burner from the back of the dryer.

WARNING:

Discontinue power to dryer before attempting

to reset hi-limit.

!