beautypg.com

American Dryer Corp. AD-15 Phase 7 User Manual

Page 7

background image

113243-1

www.amdry.com

5

DRYER ENCLOSURE REQUIREMENTS

Bulkheads and partitions should be made of noncombustible

materials and must be located a minimum of

12-inches (30.48 cm) above the dryer’s outer top; 18-inches

(45.72 cm) for steam dryers, except along the front of the

dryer which may be closed if desired.

X = 12-inch (30.48 cm) minimum, 24-inches (60.96 cm) is

suggested for ease of maintenance.

*

1-inch (2.54 cm) maximum for electric dryers.

** 18-inch (45.72 cm) minimum for steam dryers.

EXHAUST REQUIREMENTS

Exhaust ductwork should be designed and installed by a

qualified professional. Improperly sized ductwork will create

excessive back pressure which results in slow drying,

increased use of energy, and shutdown of the burner by the

airflow (sail) switch, burner hi-limit, or lint chamber hi-heat

protector thermostat. The dryer must be installed with a

proper exhaust duct connection to the outside.

NOTE:

Air considerations are important for proper and

efficient operation.

Allowances must be made for opening the

control door.

Dryers may be positioned sidewall to sidewall. However, a

1/16” (1.587 mm) minimum allowance must be made for the

opening and closing of the control door and the lint door. It is

suggested that the dryer be positioned about 2 feet (0.61

meters) away from the nearest obstruction for ease of

installation, maintenance, and service (to be measured from

the back guard). Refer to the illustration below for details.

FRESH AIR SUPPLY REQUIREMENTS

Air supply (make-up air) must be given careful consideration

to ensure proper performance of each dryer. An unrestricted

source of air is necessary for each dryer. As a general rule,

an unrestricted air entrance from the outdoors (atmosphere)

of a minimum of 1 square foot (0.09 square meters) is required

for each dryer. If registers or louvers are installed over the

openings, then the area must be increased. It is not

necessary to have separate make-up air openings for each

dryer. Common make-up air openings are acceptable.

However, they must be set up in such a manner that the

make-up air is distributed equally to the dryers. The dryer

must be installed with provisions for adequate combustion

and make-up air supply.

EXAMPLE: For a bank of eight (8) dryers, two (2)

unrestricted openings measuring 2

feet x 2 feet (0.61 meters x 0.61 meters)

are acceptable.

IMPORTANT:

Make-up air openings should not be located

in an area directly near where exhaust vents

exit the building.

Allowances must be made for remote or constricting

passageways or where dryers are located at excessive

altitudes or predominantly low pressure areas.

IMPORTANT:

Make-up air must be provided from a source

free of dry cleaning solvent fumes. Make-up air

that is contaminated by dry cleaning solvent

fumes will result in irreparable damage to the

motors and other dryer components.

NOTE:

Component failure due to dry cleaning solvent

fumes will VOID THE WARRANTY.

!

!

!