Digital Dosing Units

45

NOTE: Turning the trim-pot to the left decreases the switching sensitivity; turning it
to the right increases the switching sensitivity.

5. Fill the dosing station until the level probe is two-thirds covered. The yellow

control lamp should now switch on again. If not, repeat Step 4.

6. Reinstall the plastic screw (M3).


NOTE: The sliding switch under the cover must be set on “0”.

Communication Protocol Interfaces

The Digital Dosing unit can be controlled remotely through the EUROMAP E17 or MODBUS

RTU protocol. Contact Sales and Service concerning this option at 810.720.7300.