Digital Dosing Units

18

Press Input button

- When “11” flashes, enter 50
- This value is the minimum input frequency.



Press Input button

When “12” flashes, enter 10

This value is the span factor.


Press Input button

When “13” flashes, enter the communication address.

− If Euromap17 is not intended to for use, enter 0.

− This value is the communication address. Only enter a value here if Euromap17

report is in use.