Device safe 1 / safe 1.1 – NORSTAT Safety Relays User Manual
Page 9
DEVICE
SAFE 1 / SAFE 1.1
Emergency stop
APPLICATIONS
and safety gate monitoring relay
APPROVALS
CE, TÜV, UL, C-UL
CONTACTS
3 normally open safety, 1 normally auxiliary closed
LED indicators for status and supply diagnostic
SPECIAL CHARACTERISTICS
With (SAFE 1.1) and without (SAFE 1) start control
LED
Power, channel 1 and channel 2
OPERATING VOLTAGE
24 V AC / DC (electronic fuse)
POWER CONSUMPTION
ca. 2,5 VA / 2,5 W
START UP DELAY / FALLBACK TIME
< 50 ms / < 100 ms
CONTACT CAPACITY max.
5 A, 250 V AC, 24 V DC
CONTACT CAPACITY min. at 24V DC (*)
1 mA
SIMULTANEITY
ENVIRONMENTAL TEMPERATURE
-25°C to + 55°C
SWITCHING CAPACITY
1250 VA (resistive load)
CONTACT SECURITY
6,3 A quick acting or 4 A time lag
OPERATING MODE
(*) We offer all devices who have a CONTACT
CAPACITY of min. 100 mA at 24 V DC with
hard gold-plated contacts. In this way the
CONTACT CAPACITY of min. 100 mA is only 4 mA.
Please ask our sales team!
CONNECTION DIAGRAM
A supply voltage must be applied via emergency stop button to terminals A1
and A2. Power LED illuminates if the emergency stop is closed. To start the
unit terminals Y2 and Y1 must be bridged with a normally open contact. The
unit works if you close this contact. At this time the contacts 13-14, 23-24
and 33-34 are closed, contact 41-42 is opened. The LEDs channel 1 and
channel 2 illuminate. In series to this start button an external contactor can
be monitored.
A1
Y1
Y2
A2
+24V 0V
Not-Halt
E-Stop
Start
FUNCTION CIRCUIT DIAGRAM
Überwachungslogik /
control logic
~
~
+
~~
=
K1
elektr.
Sicherung /
electr. fuse
A1
(+)
A2
(-)
Y1 Y2
14
K2
K2
24 34
42
K1
13 23 33
41
Certifications according to
Safety relevant substance data
Depending on wiring (only max. values are given)
EN ISO 13849-1: PLd, Cat. 3 (***see product-navigator page 4)
MTTFd: 37,57 years / high, DC: 90% / medium,
CCF: achieved
NORSTAT INC. 300 Roundhill Dr. Rockaway, NJ 07866
Tel: 973-586-2500 Fax: 973-586-1590 www.norstat.com