beautypg.com

Safety on bus device safe il1 / il2 / ill / il2 – NORSTAT Safety Relays User Manual

Page 34

background image

Safety on Bus

DEVICE

SAFE IL1 / IL2 / ILL / IL2

Interbus INLINE devices ( emergency stop, safety gate controlling,

APPLICATIONS

two hand controlling, safety light curtains/barriers)

APPROVALS

CE, TÜV

CONTACTS

1 normally open safety

LED indicators for status and supply diagnostic

SPECIAL CHARACTERISTICS

diagnostic with fieldbus, integration in the inline system

LED

Channel 1, channel 2, US, UM, diagnostic

24 V DC

OPERATING VOLTAGE

POWER CONSUMPTION

ca. 1,7 W

START UP DELAY / FALLBACK TIME

-- / < 20 ms

CONTACT CAPACITY max.

4A DC, 24 V

CONTACT CAPACITY min. at 24V DC (*)

10 mA

SIMULTANEITY

ENVIRONMENTAL TEMPERATURE

-25°C to +55°C

SWITCHING CAPACITY

120 W

CONTACT SECURITY

4 A time lag

OPERATING MODE

(*) We offer all devices who have a CONTACT

CAPACITY of min. 100 mA at 24 V DC with

hard gold-plated contacts. In this way the

CONTACT CAPACITY of min. 100 mA is only 4 mA.

Please ask our sales team!

CONNECTION DIAGRAM

For the operation of the device the device must be connected into a Inline

station. The voltage supply is taken over the Inlinesystem. The LED "UM"

illuminates. For a detailed description please see appropriate manuals.

Please pay attention to our circuit breaker SAFE IL2.

Sales only on inquiry

FUNCTION CIRCUIT DIAGRAM

Notice: please ask for detailed documentation.

Certifications according to

Safety relevant substance data

Depending on wiring (only max. values are given)

NORSTAT INC. 300 Roundhill Dr. Rockaway, NJ 07866

Tel: 973-586-2500 Fax: 973-586-1590 www.norstat.com