Device safe cl – NORSTAT Safety Relays User Manual
Page 23
DEVICE
SAFE CL
Safety controller
APPLICATIONS
for safety light barriers and safety light curtain
APPROVALS
CE, TÜV, UL, C-UL
CONTACTS
4 OSSD
LED indicators for status and supply diagnostic
SPECIAL CHARACTERISTICS
wearless contacts, "AND" function between several SAFE C possible,
automatic start possible
LED
Power, channel 1, channel 2
24 V DC ( + 25 - 20 % )
OPERATING VOLTAGE
Overvoltage protection
POWER CONSUMPTION
ca. 3 W
START UP DELAY / FALLBACK TIME
< 70 ms / < 30 ms
CONTACT CAPACITY max.
total current bis 1,8 A
CONTACT CAPACITY min. at 24V DC (*)
infinite
SIMULTANEITY
S12 before S22 < 0,5 s / S22 before S12 infinite
ENVIRONMENTAL TEMPERATURE
-25°C to +55°C
SWITCHING CAPACITY
to 43 W
CONTACT SECURITY
short circuit proof
OPERATING MODE
(*) We offer all devices who have a CONTACT
CAPACITY of min. 100 mA at 24 V DC with
hard gold-plated contacts. In this way the
CONTACT CAPACITY of min. 100 mA is only 4 mA.
Please ask our sales team!
CONNECTION DIAGRAM
Even ESPE type 4 with OSSDs and relay contacts as well as ESPE type 2
with one OSSD and test input are supported. Monitoring of movement
direction is available by different simultaneousnesses.
BWS - Empfänger
ESPE - receiver
24VAC/DC
S21 S34
A1 A2
S22 S12
44 34 24 14
start
GND
PNP PNP
S32
S11 S33 S35
S36 S37
FUNCTION CIRCUIT DIAGRAM
A1 A2
Power
Input circuits
S12
S22
S34
S35
S36
Output
circuits
Combination
circuit
S11 S21
S33
MCU1
MCU2
Saf
et
y o
ut
pu
t ci
rc
ui
ts
14
24
34
44
S32
S37
Certifications according to
Safety relevant substance data
Depending on wiring (only max. values are given)
EN ISO 13849-1/ EN 61508: PLe, Cat. 4 / SIL3
MTTFd: 163 years / high, DC: high, CCF: achieved
PFH: 2,87*10
-9 1
/
h
, PFD: 2,01*10
-6 1
/
h,
SFF: 0,9573
NORSTAT INC. 300 Roundhill Dr. Rockaway, NJ 07866
Tel: 973-586-2500 Fax: 973-586-1590 www.norstat.com