Device safe t on – NORSTAT Safety Relays User Manual
Page 15
DEVICE
SAFE T ON
Emergency stop and safety gate monitoring relay with immediate and
APPLICATIONS
delayed outputs
APPROVALS
CE, TÜV, UL, C-UL
CONTACTS
2 n.o., 2 n.o. start up delayed, 1 n.c.
cross circuit protection or single-channel
SPECIAL CHARACTERISTICS
Time delay 0,05s - 600s in 64 steps,
automatic or manually start with start button
LED
Power, channel 1, cannel 2, channel 1 and 2 delayed-on energisation
OPERATING VOLTAGE
24 V AC / DC ( + 25 - 20 % ) (electronic fuse )
POWER CONSUMPTION
ca. 4,8 W
START UP DELAY / FALLBACK TIME
400 ms / 30 ms
CONTACT CAPACITY max.
6 A, 250 V AC, 24 V DC
CONTACT CAPACITY min. at 24V DC (*)
6 mA
SIMULTANEITY
no
ENVIRONMENTAL TEMPERATURE
-25°C to +55°C
SWITCHING CAPACITY
1500 VA (ohm load)
CONTACT SECURITY
3,6A
OPERATING MODE
(*) We offer all devices who have a CONTACT
CAPACITY of min. 100 mA at 24 V DC with
hard gold-plated contacts. In this way the
CONTACT CAPACITY of min. 100 mA is only 4 mA.
Please ask our sales team!
CONNECTION DIAGRAM
If the input circuits S11, S12 and S21, S22 are closed and the start button is
released, the safety circuits 13-14, 23-24 will close. By pressing the stop
button, the safety circuits 13-14 and 23-24 open. After the set time period
has elapsed, the relay K3 and K4 energise. The safety gate switch is
released and the safety gate can be opened. By pressing the start button
the relay K3 and K4 are energised, K1 and K2 energised and close the
safety circuits 13-14 and 23-24.
S21 S22 A2
48
47
A1 S11 S12
57 58
S10 S33
31
S35 S34
32
13 14
23 24
SAFE T ON
START
[
SK
ÜK
SK = Sicherheitskreis / Safety circuit
ÜK = Überwachungskreis / Monitoring circuit
L+
Not-Halt
E-Stop
Auf
FUNCTION CIRCUIT DIAGRAM
~~
Power
Logic
A1 S35 S10 S11 S12 13 23 31
47
57
58
48
32
24
14
S22
S21
S34
S33
A2
K1
K2
K3
K4
t = 0,05s....600s
Certifications according to
Safety relevant substance data
Depending on wiring (only max. values are given)
EN ISO 13849-1 / EN 62061: PLe, Cat. 4 / SIL3, SIL CL3
PFH: 3,4*10
-9 1
/
h
, PFD: 9,32*10
-6 1
/
h
, SFF: 94%
MTTFd: >100 years / high, DC: 99% / high, CCF: achieved
NORSTAT INC. 300 Roundhill Dr. Rockaway, NJ 07866
Tel: 973-586-2500 Fax: 973-586-1590 www.norstat.com