Device rs-nagl / rs-nagl.1 – NORSTAT Safety Relays User Manual
Page 24
DEVICE
RS-NAGL / RS-NAGL.1
Emergency stop relay
APPLICATIONS
for safety light curtains / barriers
APPROVALS
CE, TÜV, UL, C-UL
CONTACTS
2 normally open safety, 1 normally auxiliary closed, 1 auxiliary n. c.
LED indicators for status and supply diagnostic
SPECIAL CHARACTERISTICS
With (NAGL) and without (NAGL.1) opposite polarity between channels
LED
Channel 1 and channel 2
RS-NAGL / L.1: 24 V DC (without galvanic disconnection)
OPERATING VOLTAGE
RS-NAGL: 48, 110-127, 230 V AC (with galvanic
24 V AC / DC (without galvanic disconnection, but with a safety
POWER CONSUMPTION
24 V DC: 2W, 24 V AC / DC: 4,5 VA, other: 4,6 VA
START UP DELAY / FALLBACK TIME
< 150 ms / < 30 ms
CONTACT CAPACITY max.
6 A, 250 V AC, 250 V DC
CONTACT CAPACITY min. at 24V DC (*)
10 mA
SIMULTANEITY
ENVIRONMENTAL TEMPERATURE
- 25°C to + 55°C
SWITCHING CAPACITY
1500 VA (resistive load), 100 W
CONTACT SECURITY
6 A quick acting (normally open) or 4 A time lag (normally closed)
OPERATING MODE
(*) We offer all devices who have a CONTACT
CAPACITY of min. 100 mA at 24 V DC with
hard gold-plated contacts. In this way the
CONTACT CAPACITY of min. 100 mA is only 4 mA.
Please ask our sales team!
CONNECTION DIAGRAM
A supply voltage must be applied at terminals A1 and A2 in order to operate
the device. If this is done there is a voltage of 24V DC at terminal T11. T12
and T22 must be wired as shown in the application examples. Contacts 13-
14, 23-24 and 63-64 open and contact 41-42 closes. In some cases, the
transmitter from the light curtains / barrier requires a test input and is
connected to output 63-64. If 63-64 does not close, the transmitter and the
receiver will not work. This output ensures that a complete system is
created. To start the unit terminal T11 must be bridged with terminal T34
through a normally open contact (reset) or the terminal T34 must receive a
24V DC impulse (short time bridging of the connection terminals T11-T34).
If the light curtains is aligned properly and the protection zone is free, the
receiver switches. At terminal T12 there is a of voltage 24V DC and at T22
is ground. After releasing the on button or interrupting the connection
between T11 and T34 the relays K1 and K4 deenergize. Safety outputs 13-
14 and 23-24 close. Contacts 53-54 and 63-64 remain closed, contacts 41-
42 open.
*Sicherheitslichtschranke Empfänger: Relaisausgänge
*
safety light curtains receiver: relay outputs
**Anschluss Sicherheitslichtschranke Sender: Testeingang
**safety light curtains transmitter: test input
T34 T11
Start
T12 T44 T22 X1 X2 63 64
** **
*
FUNCTION CIRCUIT DIAGRAM
~
~
T44
PE
+
-
K1
K3
T1
R4
K2
K1
X1
T34
T11
Start
24
14
42
K2
K3
64
T12
X2
T22
23
13
41
63
A1 (+) A2 (-)
Certifications according to
Safety relevant substance data
Depending on wiring (only max. values are given)
EN ISO 13849-1: PLe, Cat.4
MTTFd: 69,05 years / high, DC: 99% / high,
CCF: achieved