beautypg.com

Expansion modules device safe x4 / safe x4.1 – NORSTAT Safety Relays User Manual

Page 28

background image

Expansion modules

DEVICE

SAFE X4 / SAFE X4.1

Expansion module

APPLICATIONS

for emergency stop relay according to VDE 0113

APPROVALS

CE, TÜV, UL, C-UL

CONTACTS

4 normally open safety and 1 normally safety closed (feedback)

With (SAFE X4) and without (SAFE X4.1) opposite polarity between

SPECIAL CHARACTERISTICS

Easy way to increase the number of contacts

Compact housing

LED

Channel 1, channel 2 and fault

48, 110-127, 230 V AC (with galvanic disconnection/transformer)

OPERATING VOLTAGE

24 V AC / DC (without galvanic disconnection, but with a safety

POWER CONSUMPTION

ca. 4 VA

START UP DELAY / FALLBACK TIME

- / < 50 ms

CONTACT CAPACITY max.

6 A, 250 V AC, 24 V DC, sum of currents < 16 A

CONTACT CAPACITY min. at 24V DC (*)

6 mA

SIMULTANEITY

ENVIRONMENTAL TEMPERATURE

- 25°C to + 55 °C

SWITCHING CAPACITY

1500 VA

CONTACT SECURITY

10 A quick acting

OPERATING MODE

(*) We offer all devices who have a CONTACT

CAPACITY of min. 100 mA at 24 V DC with

hard gold-plated contacts. In this way the

CONTACT CAPACITY of min. 100 mA is only 4 mA.

Please ask our sales team!

CONNECTION DIAGRAM

The expansion module is used to increase the number of outputs of a safety

relay according to VDE 0113. Several expansion modules can be connected

to one safety relay. A supply voltage must be applied at terminals A1 and

A2 in order to operate the device. If this is done there is a voltage of 24V DC

at terminal U1. Terminals K21 and K1 must be wired as shown in the

application examples. To start the module, closed safety circuits from the

safety relay must be connected with K21 and K1 and contacts 13-14,

23-24, 33-34, 43-44, 53-53, 63-64, 73-74 and 83-84 close. The LED´s

channel 1 and 2 illuminate. The fault LED illuminates if one or more safety

circuits are open. The fault LED will be illuminated while the expansion

module relay is operational.

For version with detachable clamps (screw - or cage clamps) ...

please ask our sales team!

U1

+ 24VDC

K21 K1

ohne Querschlusssicherheit /

without opposite polarity

mit Querschlusssicherheit /

with opposite polarity

13

14

23

24

U1

+ 24VDC

K1

U22

0 V

13

14

23

24

K21

FUNCTION CIRCUIT DIAGRAM

elektr. Sicherung

Transformator /

electr. Fuse

transformer

Überwachungslogik /

-

AC

A1

K1

Y2

DC

+

K2

14 24 34

44

Y1

Controller Logic

A2

U1 U22

K1

K21

13 23 33

43

Certifications according to

Safety relevant substance data

Depending on wiring (only max. values are given)

EN ISO 13849-1: PLe, Cat.4

MTTFd: 185 years / high, DC: 99% / high,

CCF: achieved

NORSTAT INC. 300 Roundhill Dr. Rockaway, NJ 07866

Tel: 973-586-2500 Fax: 973-586-1590 www.norstat.com