Muting device rs-nagu.12 – NORSTAT Safety Relays User Manual
Page 32
Muting
DEVICE
RS-NAGU.12
Muting control
APPLICATIONS
APPROVALS
CE, TÜV
CONTACTS
3 electronic safety semiconductor outputs (2 PNP / 1 NPN)
4 muting sensors connectable
SPECIAL CHARACTERISTICS
Control of filament of external muting lamp
Suitable for ESPE-2 with selftest
LED
Power, channel 1, channel 2, fault and restart interlock
OPERATING VOLTAGE
24 V DC
POWER CONSUMPTION
10 W (up to 60 W including peripheral devices)
START UP DELAY / FALLBACK TIME
< 6 ms
CONTACT CAPACITY max.
0,7 - 1,5 A
(*2)
, 24 V DC
CONTACT CAPACITY min. at 24V DC (*)
1 mA
SIMULTANEITY
Simultaneous of the muting sensors : 3 s
ENVIRONMENTAL TEMPERATURE
- 25°C to + 55°C
SWITCHING CAPACITY
17 W
CONTACT SECURITY
outputs are permanently short circuit proof
OPERATING MODE
(*) We offer all devices who have a CONTACT
CAPACITY of min. 100 mA at 24 V DC with
hard gold-plated contacts. In this way the
CONTACT CAPACITY of min. 100 mA is only 4 mA.
Please ask our sales team!
CONNECTION DIAGRAM
RS-NAGU.12 could be used together with safety light barriers and safety
light curtains with safety category 2 which have a selftest. The RS-NAGU.12
is used for muting of safety light barriers and safety light curtains. So that
material - transport to or from a machine can be done. Applications can be
found in the automotive industry, packaging machines or at highly
automated production systems. The differentiation between human beings
and material flow is done with up to four muting sensors or two safety light
barriers. Inductive sensors or mechanical switches can also be used as
muting sensors. After connection as per application guide, the device will be
ready as soon as the power LED and channel are illuminated. If LED
channel 1 is blinking, a fault exists or a wrong connection has been made.
In ready condition the RS-NAGU.12 can be started by pushing the start
key. If it cannot be started, then at least one of the muting sensors is
blocked or not connected correctly. If a muting sensor is blocked by material
supply, a muting can be initiated by actuation of the key switch. If the light
barrier is interrupted after a muting cycle, RS-NAGU.12 can be activated by
pushing the start key after the failure has been fixed. As soon
as muting sensors 1 and 2, respectively 3 and 4 will be activated within 3
sec.,
the RS-NAGU.12 will initiate a muting cycle. Interruption of the light barrier
will
not cause a stop of the machine. If 3 of the 4 muting sensors are
deactivated,
the muting cycle will end after 0.25 sec.
FUNCTION CIRCUIT DIAGRAM
(*2)
1,5 A permanent output (1 output) up to 4,5 A start-up current
(t<1s, Uv>21,6V),
1 A permanent current (2 outputs), 0,7 A permanent current
(3 outputs)
Notice: please ask for detailed documentation.
Certifications according to
Safety relevant substance data
Depending on wiring (only max. values are given)
EN ISO 13849-1: PLe, Cat.4
MTTFd: >100 years / high, DC: 99% / high,
CCF: achieved