1.8 USS
– Frequency inverter settings
BU 0050 GB-3111
Subject to technical amendments
57
Parameter
Setting value / Description / Note
Comments
P740
... [-01]
…
... [-23]
Process data Bus In
(Process data Bus In)
SK 540E / SK 545E
0000 ... FFFF (hex)
This
parameter
informs
about the actual control
word and the setpoints that
are transferred via the bus
systems.
For display, a BUS system
must be selected in P509
[-01 ] = Control word
Control word, source from
P509.
[-02] = Setpoint 1
[-03] = Setpoint 2
[-04] = Setpoint 3
[-05] = Setpoint 4
[-06] = Setpoint 5
Setpoint data from main
setpoint (P510 [-01]).
[-07] = Bus I/O In Bits (P480)
The displayed value depicts all
Bus In bit sources linked with
OR.
[-08] = Parameter data In 1
[-09] = Parameter data In 2
[-10] = Parameter data In 3
[-11] = Parameter data In 4
[-12] = Parameter data In 5
Data during parameter transfer:
Order label (AK),
Parameter
number (PNU),
Index (IND),
Parameter value (PWE 1/2)
[-13] = Setpoint 1
[-14] = Setpoint 2
[-15] = Setpoint 3
[-16] = Setpoint 4
[-17] = Setpoint 5
Setpoint data from the master
function value (Broadcast), if
P509 = 9/10
(P510 [-02])
[-18] = Control word PLC
Control word, source PLC
[-19] = Setpoint 1
[-20] = Setpoint 2
[-21] = Setpoint 3
[-22] = Setpoint 4
[-23] = Setpoint 5
Setpoint data from the PLC.
P741
... [-01]
…
... [-06]
Process data Bus Out
(Process data Bus Out)
SK 300E, SK 700E, SK 750E
0000 ... FFFF (hex)
Displays the actual status word and actual values.
[-01] = Status word
[-02] = Actual value 1 (P543)
[-03] = Actual value 1 High byte
[-04] = Actual value 2 (P544)
[-05] = Actual value 3 (P545)
[-06] = Bus I/O Out Bits (P481)