Enable with 50% setpoint

A frequency inverter with the USS address 10, which is in "Standby" status (Section 1.6.2) is to be enabled for
clockwise rotation with 50% setpoint. The last response telegram was received as follows in the controller.

Procedure:

Check last status word (ZSW 0A 31)

Set address (Address 0A)

Generate control word (STW 04 7F)

Generate setpoint (2000 hex)

Send telegram

Check response telegram (ZSW 0F 37)

Details:

Starting requirement (status word of frequency inverter)

0

1

2

3

4

5

6

7

8

9

10

11

12

13

STX

LGE

ADR

PKE

PKE

IND

IND

PWE

PWE

ZSW

ZSW

IW1

IW1

BCC

02

0C

0A

00

00

00

00

00

00

0B

31

00

00

37

The following telegram must be sent to the inverter

0

1

2

3

4

5

6

7

8

9

10

11

12

13

STX

LGE

ADR

PKE

PKE

IND

IND

PWE

PWE

STW

STW

SW1

SW1

BCC

02

0C

0A

00

00

00

00

00

00

04

7F

20

00

5F

The frequency inverter accelerates the motor in the ramp. When the inverter has reached the 50% setpoint, it
responds with the following telegram.

0

1

2

3

4

5

6

7

8

9

10

11

12

13

STX

LGE

ADR

PKE

PKE

IND

IND

PWE

PWE

ZSW

ZSW

IW1

IW1

BCC

02

0C

0A

00

00

00

00

00

00

0F

37

20

00

1C

Note:

The status of MFR 1 is indicated in Bit 10 of the response telegram. Depending on the
programmed function and status, the status word may differ.