1.6.4

Writing a parameter

When transferring parameter orders, it must be taken into account that the slave does not immediately respond
to orders in the parameter channel of the master telegram, but a positive response can be delayed by one or
more communication cycles. The master must therefore repeat the required order until the corresponding slave
response is received.

The acceleration time parameter (USS No. = 102

dec

/ 66

hex

) of a frequency inverter with the USS address 3, is

to be set to the value 10sec in parameter set 2. No process data is transferred.

As the acceleration time has an internal inverter resolution of 0.01sec, a parameter value of
10 / 0.01 = 1000 (3E8

hex

) must be transferred. PPO1 was selected as the PPO type.

Procedure:

Set address (Address 03)

Select parameter (P 102

dec

/ P 66

hex

)

Select order label (2 = change parameter value (word))

Select parameter set 2 (IND = 01)

Set parameter word (1000

dec

/ 3E8

HEX

)

Send telegram

Check response telegram

The telegram is composed as follows in hexadecimal notation:

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

STX

LGE

ADR

PKE

PKE

IND

IND

PWE

PWE

PWE

PWE

STW

STW

SW1

SW1

BCC

02

0E

03

20

66

00

01

00

00

03

E8

00

00

00

00

80

When the order has been fully implemented by the inverter, it responds with

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

STX

LGE

ADR

PKE

PKE

IND

IND

PWE

PWE

PWE

PWE

ZSW

ZSW

IW1

IW1

BCC

02

0E

03

10

66

00

01

00

00

03

E8

09

31

00

00

88