Parameter
Setting value / Description / Note
Comments
P548 (P)
Function Bus setpoint 3
(Function of bus setpoint 3)
except SK 54xE
0 ... 46 (47)
{ 0 }
In this parameter, a function is assigned to the delivered setpoint 3 (SW3) for bus control. This is
only available if P546
3 (only applies for SK 700E / SK 750E).
For setting values, see parameter (P547)
1.8.1.3
Information parameters
NOTE
As of firmware version V1.9 R0 for the SK 500E series, not only current error messages but
also warnings and information messages can be displayed via the parameter. In this context,
the parameter (P700) has been converted into an array parameter. I.e. error messages are
displayed in (P700 [-01]), warnings in (P700[-02]), and information in (P700 [-03]).
For all other series (SK 300E, SK 700E, SK 750E), parameter (P700) still only indicates error
messages.
Parameter
Setting value / Description / Note
Comments
P740
... [-01]
…
... [-06
]
Process data Bus In
(Process data Bus In)
SK 300E, SK 700E, SK 750E
0000 ... FFFF (hex)
Displays the actual control word and the setpoints.
[-01] = Control word
[-02] = Setpoint 1 (P546)
[-03] = Setpoint 1 High byte
[-04] = Setpoint 2 (P547)
[-05] = Setpoint 3 (P548)
[-06] = Bus I/O In Bits (P480)
P740
... [-01]
…
... [-13]
Process data Bus In
(Process data Bus In)
SK 500E to SK 535E
0000 ... FFFF (hex)
This parameter informs about
the actual control word and
the
setpoints
that
are
transferred
via
the
bus
systems.
[-01 ] = Control word
Control word, source from
P509.
[-02] = Setpoint 1
[-03] = Setpoint 2
[-04] = Setpoint 3
Setpoint data from main
setpoint P510 - 01.
[-05] = Bus I/O In Bits (P480)
The displayed value depicts
all Bus In bit sources linked
with OR.
[-06] = Parameter data In 1
[-07] = Parameter data In 2
[-08] = Parameter data In 3
[-09] = Parameter data In 4
[-10] = Parameter data In 5
Data during parameter
transfer.
[-11] = Setpoint 1
[-12] = Setpoint 2
[-13] = Setpoint 3
Setpoint data from auxiliary
setpoint P510 - 02.