beautypg.com

5 reading the acceleration time parameter, Reading the acceleration time parameter – NORD Drivesystems BU0050 User Manual

Page 48

background image

NORD USS and Modbus RTU Manual

48

Subject to technical amendments

BU 0050 GB-3111

1.6.5

Reading the acceleration time parameter

The acceleration time parameter (USS No. = 102

dec

/ 66

hex

) in parameter set 2 of a frequency inverter with the

USS address 3, is to be read out. No process data is transferred.

Procedure:

Set address (Address 03)

Generate parameter label (PKE 10 66)

Select parameter set 2 (IND = 01)

Send telegram

Check response telegram (PWE = 3E8)

Details:

0

1

2

3

4

5

6

7

8

9

10

11

12

13

STX

LGE

ADR

PKE

PKE

IND

IND

PWE

PWE

STW

STW

SW1

SW1

BCC

02

0C

03

10

66

00

01

00

00

00

00

00

00

7A

The response telegram of the slave contains the required parameter value in internal standardisation and
could be as follows:

0

1

2

3

4

5

6

7

8

9

10

11

12

13

STX

LGE

ADR

PKE

PKE

IND

IND

PWE

PWE

ZSW

ZSW

IW1

IW1

BCC

02

0C

03

10

66

00

01

03

E8

0B

31

20

00

A8

The value sent in PWE2 is C8

HEX

corresponding to 1000

DEC

, with a resolution of 0.01 seconds, this

corresponds to an acceleration time of 1000 * 0.01 = 10 seconds

 10 / 0.01 = 1000 (3E8

hex

)