NORD Drivesystems BU0050 User Manual

Page 55

background image

1.8 USS

– Frequency inverter settings

BU 0050 GB-3111

Subject to technical amendments

55

Parameter

Setting value / Description / Note

Comments

P546 (P)

Function Bus setpoint 1

(Function of bus setpoint 1)

0 ... 7 (47)

{ 1 }

In this parameter, a function is assigned to the delivered setpoint 1 (SW1) for bus control.

NOTE:

Further details can be found in the respective FI manual or in the description of P400.

SK 300E, SK 700E SK 750E

0 =
Off
1 = Setpoint frequency (16 bit)
2 = 16 Bit setpoint position

(only POSICON SK700/750E)

3 = 32 Bit setpoint position

(only POSICON, SK700/750E and if
PPO- type 2 or 4 are selected)

4 = Control terminals POSICON (only

POSICON, SK700/750E, 16Bit)

5 = Setpoint position (16 Bit) increment

1

(onlyPOSICON, SK700/750E)

6 = Setpoint position (32 Bit) increment

1

(onlyPOSICON, SK700/750E)

7 = Bus IO In Bits 0-7

SK 500E

0 = Off
1 = Setpoint frequency (16 bit)
2 = Torque current limit (P112)
3 = Actual frequency PID
4 = Frequency addition
5 = Frequency subtraction
6 = Current limit (P536)
7 = Maximum frequency (P105)
8 = Actual PID frequency limited
9 = Actual PID frequency monitored

10 = Torque servo mode (P300)
11 = Lead torque (P214)
12 = Reserved
13 = Multiplication
14 = PI process controller actual value
15 = PI process controller setpoint
16 = PI process controller lead
17 = Digital In bits 0...7
18 = Reserved
19 = Set relay (P434/441/450/455=38)
20 = Set analog output (P418=31)
21 = Setpoint position Low word

(SK 530E and above)

22 = Setpoint position High word

(SK 530E and above)

23 = Setpoint position increment Low word

(SK 530E and above)

24 = Setpoint position increment High word

(SK 530E and above)

25 = ... 45 reserved
46 = Setpoint torque process controller
47 = Gearing transfer factor

NOTE:

For SK 540 and SK545E 5 setpoints are available. These are all set in parameter
P546, which is divided into 5 array elements for this purpose. Parameters P547
and P548 are not required for this inverter version.

[-01] = Bus setpoint 1

[-02] = Bus setpoint 2

[-03] = Bus setpoint 3

[-04] = Bus setpoint 4

[-05] = Bus setpoint 5

P547 (P)

Function Bus setpoint 2

(Function of bus setpoint 2)

except SK 54xE

0 ... 46 (47)

{ 0 }

In this parameter, a function is assigned to the delivered setpoint 2 (SW2) for bus control.

0 = Off
1 = Setpoint frequency
2 = Torque current limit (P112)
3 = Actual frequency PID
4 = Frequency addition
5 = Frequency subtraction
6 = Current limit (not SK 300E)
7 = Maximum frequency (not SK 300E)
8 = Actual PID frequency limited
9 = Actual PID frequency monitored
10 = Torque (not SK 300E)
11 = Torque lead (not SK 300E)
12 = Control terminals POSICON (not

SK 300E)

13 = Multiplication (not SK 300E)
14 = PI process controller actual value

15 = PI process controller setpoint
16 = PI process controller lead
17 = Digital In bits 0...7
18 = Curve travel calculator (not SK 300E)
19 = Set relay
20 = Set analog output
21 = Setpoint position Low word

(SK 530E and above)

22 = Setpoint position High word

(SK 530E and above)

23 = Setpoint position increment Low word

(SK 530E and above)

24 = Setpoint position increment High word

(SK 530E and above)

25 = ... 45 reserved

46 = Setpoint, torque process controller

(not SK 300E)

47 = Gearing transfer factor (only SK 500E)