beautypg.com

2 ppo types – NORD Drivesystems BU0050 User Manual

Page 27

background image

1.5 USS - Data transfer

BU 0050 GB-3111

Subject to technical amendments

27

1.5.2

PPO types

For cyclic data traffic, the Parameter- Process data Object (PPO) with which the process data (PZD) and
parameters (PKW) are transferred from the master to the frequency inverter is defined. The frequency
inverter can process PPO types 1, 2, 3 or 4.

Type

Task

PPO1

extended parameter data telegram with 32 bit parameter values and process data

PPO2

Telegram with extended process data (main and two auxiliary setpoint values) and 32 bit parameter value

PPO3

Process data telegram with main setpoint value without parameter data

PPO4

extended process data telegram with main and auxiliary setpoint values without parameter data

PPO3 and PPO4 are purely process data objects for applications which do not require parameter
processing.

Abbreviations used:

PPO

Parameter Process data Object

STW

Control word

PKW

Parameter identifier Value

ZSW

Status word

PZD

Process data

SW1..3

Setpoints 1-3

PKE

Parameter identifier

IW1..3

Actual values 1-3

IND

Index

PWE

Parameter Value

Note::

An SPS can normally only consistently transfer double words by means of I/O memory access.
For longer data formats (PKW channel always / PZD data with PPO2 or PPO4) system functions
(e.g. SFC 14, consistent data reading / SFC15, consistent data writing) must be used.

NOTE

Because of the protocol specification, for PPO types 2 and 4 6 words must be reserved for

the address area of the process data (PZD). The two last words are not used for the process
data telegrams and are therefore merely reserve areas.