beautypg.com

8 frequency inverter settings, 1 frequency inverter bus parameters, 8 frequency inverter settings 1.8.1 – NORD Drivesystems BU0050 User Manual

Page 50

background image

NORD USS and Modbus RTU Manual

50

Subject to technical amendments

BU 0050 GB-3111

1.8 Frequency Inverter Settings

1.8.1

Frequency inverter bus parameters

To operate the inverter with the USS protocol, the bus must be connected to the master and some settings
must be made on the frequency inverter.

The frequency inverter can always be parameterised. Control of the inverter via USS can be activated by
setting parameter P509 to value 2, 3 or 4 (for SK 500E to 2) (see below). In order to access the inverter via
the control unit, only the baud rate in P511 and the inverter address P512 need to be set.

The telegram down time P513 can be selected depending on the USS system.

1.8.1.1

Control clamp parameters

Parameter

Setting value / Description / Note

Comments

P480 ..[-01]

...

.. [-12]

Function BusIO In Bits

(Function of Bus I/O In Bits)

0 ... 72

{ 0 }

The Bus I/O In Bits are perceived as digital inputs. They can be set to the same functions as the digital
inputs (See P420…of the respective FI manual).

[-01]= Bus I/O In Bit 0

[-02]= Bus I/O In Bit 1

[-03]= Bus I/O In Bit 2

[-04]= Bus I/O In Bit 3

[-05]= Bus I/O In Bit 4

[-06]= Bus I/O In Bit 5

[-07]= Bus I/O In Bit 6

[-08]= Bus I/O In Bit 7

[-09]= Flag 1 (only SK 500E)

[-10]= Flag 2 (only SK 500E)

[-11]= Bit 8 BUS control word (only for SK 500E)

[-12]= Bit 9 BUS control word (only for SK 500E)

P481 .. [-01]

...

.. [-10]

Function BusIO Out Bits

(Function of Bus I/O Out Bits)

0 ... 39

{ 0 }

The bus I/O Out bits are perceived as multi-function relay outputs. They can be set to the same functions
as the digital inputs (See P434…of the respective FI manual).

[-01]= Bus I/O Out Bit 0

[-02]= Bus I/O Out Bit 1

[-03]= Bus I/O Out Bit 2

[-04]= Bus I/O Out Bit 3

[-05]= Bus I/O Out Bit 4

[-06]= Bus I/O Out Bit 5

[-07]= Bus I/O Out Bit 6 / Flag 1

[-08]= Bus I/O Out Bit 7 / Flag 2

[-09]= Bit 10 BUS status word (only for SK 500E)

[-10]= Bit 13 BUS status word (only for SK 500E)

P482 .. [-01]

...

.. [-10]

Stand. BusIO Out Bits

(Standardisation of Bus I/O Out Bits)

-

400 … 400 %

{ 100 }

Adjustment of the limit values of the relay functions/Bus Out Bits. For a negative value, the output
function will be output negative.

When the limit value is reached and the setting values are positive, the relay contact closes, with
negative setting values the relay contact opens.

P483 .. [-01]

...

.. [-10]

Hyst. BusIO Out Bits

(Hysteresis of Bus I/O Out Bits)

1 … 100 %

{ 10 }

Difference between switch-on and switch-off point to prevent oscillation of the output signal.