Dwyer ULSS User Manual

Page 9

background image

Rev 5 

MN890570 

9 of 30 

ULSX‐CAL CONFIGURATION 

Step Seven 

This section of ULSX‐CAL is where you select the application’s configuration settings.  Start from the top and 
work to the bottom, choosing the selections that are applicable to your configuration.  “Not Applicable” will 
automatically show when a selection doesn’t apply to your configuration settings, and you may move on.  All 
configuration settings must be selected or have “Not Applicable” before you can continue to the next step.  
Note:  Pressing the Clear Screen button will reset the configuration table and allow access to all of the features. 
 

 

Number of Pumps:  This feature allows you to select the number of 
pumps or valves used with Series ULS.  This is the setting that activates 
the control capabilities of up to two relays.  Control relays are often 
referred to as latching relays.    

o

Switch/Alarms  Only  –  The  relays  will  be  standard  single  point 
relays (High and/or Low alarms).  Relays are non‐latching.  

o

1‐  Pump/Valve  –  One  relay  will  be  configured  as  a  control  or 
latching relay (relay will have a start level and a separate stop 
level).    Use  this  setting  to  control  one  pump  or  valve  for 
automatic filling or emptying of a tank. 

o

2‐Pumps/Valves  –  Two  relays  are  configured  as  control  or 
latching relays.  Each relay will have a unique start level and a 
common  stop  level.    Use  this  setting  to  control  two  pumps  or 
valves for automatic filling or emptying of a tank. 

o

4‐20mA Transmitter Only – This setting will disengage all of the 
relays.    Use  this  function  if  you  are  not  using  any  relays  and 
using only the 4‐20 mA current output. 

Note: Right click on any menu that you may have questions on to open the help menu. 

Note: To reset, press the Clear Screen button. 
 
 

 