Caleffi 6000 User Manual
Page 44

19
Relay
contact
for
recirculation
pump
and
second
storage thermostat
Here following the wiring diagram of relay 1 with a clock for
managing the recirculation pump times.
Here following the wiring diagram of relay 3 for connection to the
second thermostat on the hot water storage.
Maintenance
Tests are carried out while in service, to regularly monitor the
performance of the mixing valve, since any loss of performance
may indicate the need for maintenance of the valve and/or the
system. During these tests, if the temperature of the mixed water is
found to have changed significantly compared with previous tests,
we recommend referring to the sections on installation and
commissioning and carrying out maintenance.
We recommend carrying out the following checks periodically to
ensure that the valve continues to keep optimum performance
levels. At least every 12 months, or more frequently if required.
1) Check and clean the strainers installed in the system
2) Check that any check valve installed at the inlet of the Caleffi
valve is functioning correctly and there is no seepage caused by
dirt.
3) The internal components of the valve can be descaled by
immersing them in a suitable descaling liquid.
This operation is essential in the case of systems that are used
seasonally, for example in hotels and similar establishments.
4) Once the maintainable components have been checked, we
recommend following the commissioning procedure again.
On the system log book, record all operations carried out.
Functional faults
A special set of alarms has been provided to help managing
possible faults that can occur in the regulator and the system.
Please refer to the “Alarms Management” section below.
L
N
Recirculation pump
Relay 1
1
2
L
N
Storage primary pump
Relay 3
T1
60°C
T2
70°C
5
6