beautypg.com

Caleffi 6000 User Manual

Page 35

background image

10

Description of indicators

Indications on LED display
On the front of the appliance there are 3 LED displays, which show the

clock time and temperature of the flow and return probes at all times.

Hour and minutes display

(24 h system).

Probe temperature display (in °C)

Resolution 1°C

Probe warning display “out of range” at the top.

(blinking)

Probe warning display “out of range” at the

bottom.

(blinking)

Probe warning display “open”

(blinking)

Probe warning display “short circuit”.

(blinking)

If the recirculation sensor has been set as “not present” or faulty in

program 0, the related display remains OFF.

LED indicators
The following LED indicators are located on the front of the appliance:

Electric supply LED:

red LED: steady ON when

mains voltage is present.

Mixing valve LED:

- red LED: ON when opening hot water
- blue LED: ON when opening cold water

Appliance OK status LED:

green LED: steadily ON when there are no faults or active

alarms.

Battery fault LED:

red LED: steady ON when there is a battery fault;

otherwise it is OFF.

Generic alarm LED:

red LED: steadily ON when there is an alarm (probe fault,

thermal shock in progress, reset)

Blinks when on low power.

Indications on LCD display
On the front of the appliance there is a green backlit alphanumeric

display with four rows of 20 characters each, for setting parameters,

scheduling operations, displaying error messages and device status.

The buttons on the front panel (“MENU”, “UP”, “DOWN” and “OK”) can

be used to scroll through the menu items to configure the appliance, set

the various parameters and view the temperature log.

Startup or Reset display
Quick display screen, showing appliance data and product reference

code:

Ok

Return

C

SW027A

LIN STO Q

000 000 011

CALEFFI

LEGIOMIX

tuesday 13/02/2006

adjustment

running

tuesday 13/02/2006

thermal shock

running

terminates in 0005

tuesday 13/02/2006

disinfection

running

tuesday 13/02/2006

cancel

thermal shock?

tuesday 13/02/2006

flow

running

tursday 13/02/2006

cancel

disinfection ?

Operating status
When the appliance is in operation, the LCD display indicates the device

status as shown in the following screens: